Ask Experts Questions for FREE Help !
Ask
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #21

    Nov 6, 2008, 04:04 PM

    I may be lost. If you have a normal residential electric water heater, you really shouldn't need a thermal expansion tank, unless your water pressure is to high, or your water temp is to high. You say your water heater is set at 120 degrees. Does it feel scalding hot at times? Maybe try checking the temp of your water with a thermometer. This problem of the leaky temp/pressure relief valve may be as simple as a fualty themostat on the electric water heater.
    EPMiller's Avatar
    EPMiller Posts: 624, Reputation: 37
    Senior Member
     
    #22

    Nov 6, 2008, 04:28 PM
    Quote Originally Posted by mygirlsdad77 View Post
    If you have a normal residential electric water heater, you really shouldnt need a thermal expansion tank, unless your water pressure is to high, or your water temp is to high. You say your water heater is set at 120 degrees. Does it feel scalding hot at times? Maybe try checking the temp of your water with a thermometer. This problem of the leaky temp/pressure relief valve may be as simple as a fualty themostat on the electric water heater.
    Mgd77,

    You are incorrect on not needing an expansion tank. On city water, there is a back-flow prevention valve at the meter that prevents contamination of the water distribution piping network in case of a loss of pressure. When you turn on a water heater full of cold water, the expansion as it heats could drive the pressure on the house above safe limits because of that back check valve. Usually the T&P valve blows off in that case. Around here it is a code requirement to have an expansion tank on any house that has city water and a water heater, which most do! :p
    EPMiller's Avatar
    EPMiller Posts: 624, Reputation: 37
    Senior Member
     
    #23

    Nov 6, 2008, 04:38 PM
    Quote Originally Posted by Quantum62 View Post
    Yup. i was referring to the expansion tank only having 8 PSI when everything is open. I would "assume" that it should read 40PSI. So you guys think the expansion tank has a ruptured bladder? Is there a way to check this w/o taking it off?

    Is 80 PSI water pressure really that high that I need a PRV? What is a standard pressure?
    Q62,

    To test your expansion tank, shut the water off at the meter, shut off the water heater, open a valve in a sink on the lowest floor and let the pressure go down to nothing. Measure the pressure in your xpn tank and if it is 8 psi, pump in some air until you get it back to it's 40psi precharge number. If the pressure just keeps leaking away (thru the open faucet), then the bladder is shot. Otherwise PUT THAT PRV ON and then precharge the xpn tank to the same pressure as the PRV setting. NO MORE and not much less. You don't want much water in there at all under normal working conditions. It should only have to take water to absorb the expansion of heating water. If you actually read the installation instructions on those things they will tell you to do what I just said.

    EPM
    ballengerb1's Avatar
    ballengerb1 Posts: 27,378, Reputation: 2280
    Home Repair & Remodeling Expert
     
    #24

    Nov 6, 2008, 04:41 PM

    I think I recommended a PRV in post #2. It's the logical thing at this point. I did however misunderstand KISS and Letme for a moment, I'm on board now guys.
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #25

    Nov 6, 2008, 04:44 PM

    Varies from state to state I guess. We are not required to install expansion tanks on potable water systems. Just boilers and the like. I guess I'm just saying that the expansion tank is most likely not the problem for pressure, temperature relief valve leaking from time to time. We have no idea where asker is from, or what codes they follow.

    I may be incorrect, for the area you live, but please do not say that I am (in general) incorrect. Kind of hurts my feelings. Lol
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #26

    Nov 6, 2008, 06:08 PM

    If Check valve (Backflow preventer) on Main then install Expansion Tank

    If Boiler Then install Expansion Tank

    If incoming water pressure is too high (>~60 PSI) [Expansion Tank Irrelevant] then install Pressure Regulator (PRV).

    OK?
    Quantum62's Avatar
    Quantum62 Posts: 8, Reputation: 1
    New Member
     
    #27

    Nov 7, 2008, 02:01 PM
    The water pressure at the tap is 80 PSI. It almost sounds to me like the expansion tank has ruptured AND I have to hig of a pressure entering the house.




    Quote Originally Posted by KeepItSimpleStupid View Post
    Let me think about it too. Air is compressible. Water is not.

    This gage is measuring water or air pressure? If it's measuring air pressure I could see it being 80 PSI. If it's measuring water pressure then I don't see it.

    But, on the same note if you have a PRV, you should not be able to get to 80 PSI at all. As say 50 PSI air is compressed by 40 PSI water, you'll end up with a 10 PSI difference.

    The expansion tank works because it has a variable air volume and that volume is pressurized just below the normal water pressure. It cannot read higher than the water pressure.

    Think about this: Can you inflate a tire to 90 PSI from a 40 PSI stream. No.

    Water is a wierd fluid. It expands when cooled and it expands when heated, but we are concerned about the heating. Heating water below the boiling point will not raise the pressure 40 PSI.

    Go buy a pressure gage that fits on a hose fitting and measure the house pressure at an outside tap. It won't be between 45-55 PSI.
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #28

    Nov 7, 2008, 02:17 PM

    Get the pressure reducing valve installed first. There is no point troubleshooting the expansion tank now.

    You do stand a chance of having a bad tank, but there is nothing pointing to that yet.

    For lots of bedtime reading material about expansion tanks, see:

    Learn About - What is thermal expansion, selecting an expansion tank, Potable vs. Non-Potable systems.
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #29

    Nov 7, 2008, 04:44 PM

    Sounds like kiss nailed it. Good luck and let us know what you decide.
    EPMiller's Avatar
    EPMiller Posts: 624, Reputation: 37
    Senior Member
     
    #30

    Nov 8, 2008, 06:21 PM
    Quote Originally Posted by mygirlsdad77 View Post
    Varies from state to state i guess. We are not required to install expansion tanks on potable water systems. Just boilers and the like. I guess im just saying that the expansion tank is most likely not the problem for pressure, temerature relief valve leaking from time to time. We have no idea where asker is from, or what codes they follow.

    I may be incorrect, for the area you live, but please do not say that i am (in general) incorrect. Kind of hurts my feelings. lol
    Sorry, I didn't mean to hurt your feelings, but I thought that was current code all over. You can see that I don't travel much! :p I will agree, an expansion tank is not needed on a city water system without any back flow prevention valves. However, I've seen leaking T&P valves that were "fixed" by nothing other than the addition of an expansion tank. But then I've also seen systems that worked fine with a back check and no expansion tank. A lot of piping helps. Around here one municipality I know of is going around and reinspecting homes and requiring back flow prevention and expansion tanks to be retrofitted. Other obvious violations are cited too, but they are bringing their systems up to date with the back flow prevention valves.
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #31

    Nov 9, 2008, 03:56 PM

    I don't travel much either, so I learn new things everyday on this site. We are not required here to have back flow preventers. No hard feelings. Thanks for the update.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Hot water heater leak [ 1 Answers ]

I noticed a puddle on the floor by my gas water heater. Checking out the source I found water dripping, very slowly, down the black flue at the top. No pipes were leaking No leak from the bottom. The next morning I had no hot water, and water was spraying out of the top of the water heater and...

Leak in slab from water pipe from water heater [ 4 Answers ]

Looks like I need help. Would like an overall on what I can expect when I talk to a plumber. And should I have all pipes replaced (house 60 years old), how long should this take, what would cost range be for job in southern CA? Should all piping be checked for cracks. House is very small so this...

Water heater leak [ 1 Answers ]

My water heater overflow drain is leakin continiously, how do I stop it?:confused:

Water Heater / TPR leak [ 2 Answers ]

I have a Reliance water heater (Aug 95) it is leaking from the TPR valve at a constant pace. I have done a bit of research and it suggest to replace the valve. Is this a difficult job? Someone commented that it's an explosion waiting to happen Everything else seems to be working great - but...

Water heater leak [ 11 Answers ]

I'm trying to make sure that I need a new water heater before I go buy one.I live in a mobile home which I purchased 3 years ago.I am assuming that the existing water heater is the original one that came with the home which would make it approx 18 years old.I work third shift and last night just...


View more questions Search