    Venting a washer drain
    I am retro fitting a laundry room in a 200 year old house. The existing drain is not vented. It will be close to impossible to install a new vent trough the roof or to tie into the existing vents in the new addition on the house where the kitchen and baths are located. Are there another ways to vent the system? The laundry room is on the first floor and I'm running new pipes in the wall from the full cellar below.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #2

    Jan 31, 2010, 06:11 AM
    Hi Coldspring...

    You can add a mechanical vent... also called an air admittance valve or AAV... see images. The vent needs to be accessible so you can't hide it in the wall or if you do you must have an access panel so you can access and change the AAV out if it fails in the future.

    MARK
    Attached Images
      
    coldspring2010's Avatar
    coldspring2010 Posts: 2, Reputation: 1
    New Member
     
    #3

    Jan 31, 2010, 12:57 PM
    Thanks Mark,

    I see from you sketch that the AAV must be down stream from the P trap for the washer and it also looks like it must be higher than the stand pipe so I can't hide it in the cellar below. I most likely then will add it to the horizontal run and install it in another wall about 6 feet from the washer. If I were to to a laundry sink next to the washer could the one vent handle them both.

    I should elaborate further on my system. The 2 inch laundry drain will run approximately 12 feet and tie into a 4 inch drain in the new addition. This drain is properly vented through the roof. Would that vent be enough for the laundry room or should I still add the AAV? If I install the AAV where I'm thinking then it will only be about 6 feet from the 4 inch drain.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #4

    Jan 31, 2010, 01:05 PM
    Actually, the AAV can be a minimum of 6" higher than the trap. I usually put it at the same height as the standpipe...;)

    You want to install the AAV within 5 feet of the washing machine PTRAP. The AAV will work for both the washing machine and a laundry sink, but I would install it at 42" off the floor if you use it for both fixtures... see image below.

    I also recommend that you install a 2" test tee for a cleanout as near to the trap as possible.

    MARK
    Attached Images
     

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Venting Washer Machine [ 3 Answers ]

Hello, Can I use an Automatic Vent device to vent a washer machine drain, or use a loop vent? Thanks. Nara

Venting an island drain [ 1 Answers ]

I'm relocating a kitchen sink onto an island. The island is "down stream" on the 4" waste line from the existing kitchen sink. Does the island require a separate vent?

Moved Washer upstairs, Q about venting [ 4 Answers ]

I wish I had discovered this forum earlier... I moved my washer/dryer upstairs and had no trouble doing the plumbing, I thought :-) It is working fine so far, but after reading some posts it seems I may should have vented the washer drain. Currently it is on a 40" stack pipe. The...

Venting for a washer. [ 3 Answers ]

I would like to add a washer hook-up in a utility room that I have. It is on the 1st floor of a 2 story home. Directly above it is a bathroom, so I have hot and cold water lines in the wall. As well as two waste pipes (a 3" from the toilet and a 2" from the sink/shower). I am assuming it is a...

Drain Venting [ 4 Answers ]

I recently purchased a house (35 yr old) in which the kitchen sink vent was removed (it was completely clogged). The plummer installed a mechanical vent for the sink drain. That works fine for the kitchen, however when a toilet is flushed, water actually backflows into the kitchen sink. I am...


View more questions Search