    Venting sewage ejector w/ a studor vent
    Hello, my home builder put drain pipes for tub, toilet and lavatory in basement floor; I'de like to know if venting my sewage ejector w/ a studor vent is up to plumbing code and if it will work for a full bath or must I dry vent it to the supplied vent in basement. Also, will venting the lavatory drain still necessary in this case.

    Thanks, Ron
    nmwirez's Avatar
    nmwirez Posts: 453, Reputation: 20
    Full Member
     
    #2

    Mar 3, 2007, 03:44 PM
    Quote Originally Posted by Doc P
    hello, my home builder put drain pipes for tub, toilet and lavatory in basement floor; I'de like to know if venting my sewage ejector w/ a studor vent is up to plumbing code and if it will work for a full bath or must I dry vent it to the supplied vent in basement. Also, will venting the lavatory drain still necessary in this case.

    Thanx, Ron
    UPC calls for direct venting to above roof or at least three feet away and above windows for residential construction. I am not familiar with 'Studor'. Is that a macerator type waste pump system? It would be a closed unit and not have a vent if it macerates.
    doug238's Avatar
    doug238 Posts: 1,560, Reputation: 62
    Ultra Member
     
    #3

    Mar 3, 2007, 09:38 PM
    A studor vent or an oatey vent is an air admittance valve [ aav ]. A sewage ejector will not work with an aav. It must be vented to a 'breathable' location. It must be able to let incoming water push a head of air and outgoing water draw air behind it.
    nmwirez's Avatar
    nmwirez Posts: 453, Reputation: 20
    Full Member
     
    #4

    Mar 4, 2007, 01:40 AM
    Quote Originally Posted by doug238
    a studor vent or an oatey vent is an air admittance valve [ aav ]. a sewage ejector will not work with an aav. it must be vented to a 'breathable' location. it must be able to let incoming water push a head of air and outgoing water draw air behind it.
    Thanks doug238, You may tell that I am out of touch here, so here is my dumb question concerning this setup. What would be the best way to correct the problem? Also is this an air gap or like a backflow valve? Thanks, nm
    doug238's Avatar
    doug238 Posts: 1,560, Reputation: 62
    Ultra Member
     
    #5

    Mar 4, 2007, 06:33 AM
    A studor vent or an oatey vent is an air admittance valve [ aav ]. A sewage ejector will not work with an aav. It must be vented to a 'breathable' location. It must be able to let incoming water push a head of air and outgoing water draw air behind it.
    An air admittance valve is a small device that is attached to the vent pipe to terminate the vent in an accessible location without completely piping the vent to the roof. It allows air to be sucked into the system but not pushed back out.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #6

    Mar 4, 2007, 09:43 AM
    Bottom line!
    The pit vent is a DEDICATED VENT. This means that it does not connect to the house system. The reason being, (as Doug explained) is that while the house vent system breaths in to relieve vacuum while the pit vent must breath both in and out. A AAV will only allow air the breath in so it's not suitable for the pit vent. Good luck, Tom

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search


Check out some similar questions!

Sump pump [ 2 Answers ]

I would like to say thank you in advance. THis is the first time I have ever dealt with a sump pump. My sump pump in the basement has gone out. I have tried draining the water; however the water level remains at the same spot. Am I just being impatient or am I doing something wrong?

Studor Vent [ 1 Answers ]

I recently got a new roof (flat) after Hurricane Wilma. My bathroom vent pipe had blown out through the roof and the roofers stupidly tarred over the drain. Not wanting to open up the roof, the contracted plumber said that a studor vent could be used instead of opening up the hole on the roof. Even...

Studor Vent Failing? [ 3 Answers ]

We have a Studor Terminal in an inside hallway closet in our home. Occasionally, when you walk by you can smell the sewer gases, the nice rotten egg smell of hydrogen sulfide. I thought these were a one way air vent system and prevented this sort of thing? Is it not functioning properly?...

Venting Basement Sump Pit [ 1 Answers ]

First a little background. I'm finishing a bathroom in my basement that was roughed in while the house was being built. I have a sump-pit that needs to be vented. Due to hvac and plumbing obstructions, I will need to extend the plumber provided vent pipe from the floor above a few inches below...

Studor vent with tow lavs [ 1 Answers ]

I have a 6 foot lav in my new addition. The bath is on the 2nd floor and there is no way to run the drain into the wall because of the joist below the wall. I am going through the floor into the 1st floor joist space with both lav drains. My question is -Can I use one studor vent for both lavs? I...


View more questions Search