Question
 
 
#1  
Old Jan 25, 2007, 07:21 AM
NormoRoy
New Member
NormoRoy is offline
 
Join Date: Jan 2007
Posts: 19
NormoRoy See this member's comment history on his/her Profile page.
Venting

I have a two part question.

1.This is new construction and I have a question related to the venting. I have a 3” horizontal pipe installed between to floor joist. Attached to this pipe is a shower (seperate), bathtub(seperate) and toilet. This is how I have laid it out starting at the end of the run, down to the where it attached to the main drain. I installed a 3” clean out, then the 2” shower stub out with trap, 3 feet away a 2” vertical vent pipe, another 2 feet away I have a 2” stub out for the bathtub. 5 feet away from that I have another 2” vertical vent pipe then about 18” away is the 3x4 closet elbow. The pipe runs approximately 12 more feet down to the main drain. Therefore I have two 2” vent pipes sandwiched in between those three fixtures. Is this ok or not?
2. My second question relates to the location of the vent stack. Are there any rules or regulations related to where the vent stack goes through the roof? Such as the length of pipe extending beyond the roof line, distance from the roof peak or roof’s edges?

Thank you.

Reply With Quote
 
     

Answers
 
 
Old Jan 25, 2007, 07:33 AM   #2  
speedball1
Plumbing Expert
speedball1 is offline
 
speedball1's Avatar
 
Join Date: Jan 2003
Location: Sarasota, Fl.
Posts: 12,679
speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.
Pay to call speedball1 for advice ($.95/min)
Call speedball1 via Skype™
I might have configured it a little different using one vent and wet venting one the fixtures but your layout sounds fine.

2. My second question relates to the location of the vent stack. Are there any rules or regulations related to where the vent stack goes through the roof? Such as the length of pipe extending beyond the roof line, distance from the roof peak or roof’s edges?

We run out vents 6" up from the roof line. The vents can be placed almost anywhere. Good luck, Tom
  Reply With Quote
 
     
 
 
Old Jan 25, 2007, 08:31 AM   #3  
NormoRoy
New Member
NormoRoy is offline
 
Join Date: Jan 2007
Posts: 19
NormoRoy See this member's comment history on his/her Profile page.
Quote:
Originally Posted by NormoRoy
I have a two part question.

1.This is new construction and I have a question related to the venting. I have a 3” horizontal pipe installed between to floor joist. Attached to this pipe is a shower (seperate), bathtub(seperate) and toilet. This is how I have laid it out starting at the end of the run, down to the where it attached to the main drain. I installed a 3” clean out, then the 2” shower stub out with trap, 3 feet away a 2” vertical vent pipe, another 2 feet away I have a 2” stub out for the bathtub. 5 feet away from that I have another 2” vertical vent pipe then about 18” away is the 3x4 closet elbow. The pipe runs approximately 12 more feet down to the main drain. Therefore I have two 2” vent pipes sandwiched in between those three fixtures. Is this ok or not?
2. My second question relates to the location of the vent stack. Are there any rules or regulations related to where the vent stack goes through the roof? Such as the length of pipe extending beyond the roof line, distance from the roof peak or roof’s edges?

Thank you.
Just another follow up question. I was reading another venting question where you listed Chapter 14, ( Vents and Venting) Section 1403.3 ( Main Vent Stack) of The Standard Plumbing Code states "Every building in which plumbing is installed shall have at least one main vent stack, of not less then 3-inches in diameter, which shall run undiminished in size and as directly as possible from the building main drain through to the open air above the roof."

My main drain is in the rear of the home. I plan on having the vent stack in the rear of the home but the bathrooms and kitchen are located in the front of the home. Therefore my venting process would be from the roof (rear of home) across the attic to front of the house down two floors. Once in the basement cross back to the rear of the house to the main drain. I guess this is not “as directly as possible”. Do you think I’ll have an issue with the inspector? Will I have to install the vent stack in the front roof?
  Reply With Quote
 
     
 
 
Old Jan 25, 2007, 09:54 AM   #4  
dclynch
Junior Member
dclynch is offline
 
Join Date: Feb 2005
Posts: 148
dclynch See this member's comment history on his/her Profile page.
Tom lives in Florida. (Lucky him!) If you are from an area that gets snow, you probably should have the vent pipe go higher up from the roof. In New England, I think most extend vents 18 inches and many go more.
  Reply With Quote
 
     
 
 
Old Jan 25, 2007, 10:03 AM   #5  
speedball1
Plumbing Expert
speedball1 is offline
 
speedball1's Avatar
 
Join Date: Jan 2003
Location: Sarasota, Fl.
Posts: 12,679
speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.
Pay to call speedball1 for advice ($.95/min)
Call speedball1 via Skype™
My main drain is in the rear of the home. I plan on having the vent stack in the rear of the home but the bathrooms and kitchen are located in the front of the home. Therefore my venting process would be from the roof (rear of home) across the attic to front of the house down two floors. Once in the basement cross back to the rear of the house to the main drain. I guess this is not “as directly as possible”. Do you think I’ll have an issue with the inspector? Will I have to install the vent stack in the front roof?

No, We do it all the time in new construction on upscale homes where the owner wants the vents located on the rear of the house and not showing on the front side. Cheers Tom
  Reply With Quote
 
     


Question Tools Search this Question
Search this Question:

Advanced Search
Display Modes

 
Similar Sponsors

Similar Questions
Question Asker Topic Answers Last Post
Just Venting daisydew Relationships 11 Jan 22, 2007 09:57 AM
sewage venting Cleopatra2 Plumbing 1 Dec 10, 2006 01:24 PM
Venting birdiemanca Plumbing 1 May 9, 2006 09:18 AM
Venting D-Man Plumbing 1 Feb 21, 2006 04:28 AM
Venting Thanks thepiman Plumbing 7 Sep 29, 2005 05:22 AM




Copyright ©2003 - 2007, Ask Me Help Desk.
All times are GMT -8. The time now is 07:50 PM.

Content Relevant URLs by vBSEO 3.0.0 RC6 © 2006, Crawlability, Inc.