| ""Where is the critical distance measured from?" If I have a 4" vent coming out of the roof, can I run horizontally from that vent in the attic to connect to my fixture? Is the distance measured horizontally from my trap that point where the vent stack rises vertically through the roof? Or is it measured horizontally from my trap to a point where I can connect to the venting system as a whole?"
It's measured from the trap to the vent as a whole.
By 1/2 bath I'm assuming that you'll be installing a lavatory. Right??
If so the lavatory vent can do up in the attic and revent back into the 4" main vent. The toilet will be wet vented by the lav vent. Critical distance doesn't come into play unless there's no opening to the outside air,(a vent).
Since your lavatory trap is right next to access to outside air,( the vent) it doesn't make any difference how long the horizontal line is to connect to that outside air. Good luck, Tom |