Quote:
|
Originally Posted by jefflax11 Thanks for the quick response. As a follow up. Do I only have 5' of length to play with from trap to waste stack? What is the draw back if it is longer, and do the same rules apply if it is a stand up shower only? |
You can "fudge" a bit on the distance, especially if you're not going to be inspected. But if you're connecting to the waste stack below where the toilet ties in then that is not acceptable. Code states that you may not discharge a major fixture, (toilet) past a unvented minor one, (your tub) If that's the case then you must "wet vent" the tub by connecting it to the lavatory drain.
The same rules apply to ALL fixtures that have traps.
Code states that the distance between trap and vent be;
1 1/4"--- 2 1/2'
1 1/2"--- 3 1/2'
2"------- 5'
3"------- 6'
4"------- 10'
Let me know the configuration you're using to vent the tub. Regards, Tom