    Toilet vent pipe diameter?
    I am installing a new toilet in a remodeled bathroom. The toilet is going to be placed where I cannot instal a vent pipe greater than 1.5" diameter because of existing obstructions. I understand that a vent pipe for a toilet should be 2" diameter minimum. Will the toilet flush properly with this small vent pipe?
    Thanks for the benefit of your experience.
    ballengerb1's Avatar
    ballengerb1 Posts: 27,378, Reputation: 2280
    Home Repair & Remodeling Expert
     
    #2

    Oct 11, 2007, 06:04 PM
    I don't have your answer but I have moved you back to the head of the list. If Speedball1 doesn't catch this Friday morning you might send him a IM, he's listed as the #1 plumbing expert, actually #1 expert out of all of us not matter the topic. My personal read is that your toilet should have a 3" or 4" vent, 1.5" will give you some gurgling and chugging but Tom will know better.
    iamgrowler's Avatar
    iamgrowler Posts: 1,421, Reputation: 110
    Ultra Member
     
    #3

    Oct 11, 2007, 08:43 PM
    Quote Originally Posted by Alan Bee
    I am installing a new toilet in a remodeled bathroom. The toilet is going to be placed where I cannot instal a vent pipe greater than 1.5" diameter because of existing obstructions. I understand that a vent pipe for a toilet should be 2" diameter minimum. Will the toilet flush properly with this small vent pipe?
    Thanks for the benefit of your experience.
    A lot of this depends on the developed length of the 1-1/2 run -- If we're talking nine or ten feet before tying into a larger vent, then the 1-1/2 will likely do fine if it's all vertical.

    Have you considered using 2" copper DWV pipe?

    2" copper DWV pipe is about an eighth inch thicker than 1-1/2 IPS piping.

    You would need a proper transition band (a shielded coupling) to transition from the 2" IPS to 2" DWV, but at least the internal diameter would still be a full 2".
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #4

    Oct 12, 2007, 07:05 AM
    I agree with growler that a 2" vent's better then a 1 1/2 one. Having said that my cose book, ( Standard Plumbing Code, Chapter 14, Section 1421.2 tells me that a 1 1/2" vent will service 10 fixture units at a maximun vent length of 100 feet. A water closet equals 4 fixture units. I ran into the same problem as Alan Bee some 30 years ago while roughing in a large church with 6 bathrooms. Because of space restrictions I vented 2 urinals,(8 fixture units) with a 1 1/2" vent. The inspector passed it but warned me that in the future he would prefer the vents to be at least 2".
    On another note,
    he's,(sic,speedball) listed as the #1 plumbing expert, actually #1 expert out of all of us not matter the topic.
    Thanks Bob for those kind words but I don't consider myself the top anything on this page. All the heavy posters,( and you know who you are) on this page are #1 top experts, You guys are out in the field working with new equipment and learning new procedures while I'm retired and out of the loop. While my plumbing experience might go back farther and I can draw on that youall are out there doing new things and using new equipment. You have knowledge that I do not and I think that should be recognized and applauded. I shall now climb down from my soap box. Regards to all, Tom

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Pipe diameter [ 3 Answers ]

Sorry I posted this in plumbing but had to move it here. I have a question about a residential two pipe boiler heating system with cast radiators. If I wanted to replace a section, or all of it, with copper is there a need to reduce the pipe diameter or should I leave it the same? Also is it...

Drain diameter ?: sink vs toilet [ 1 Answers ]

Tom, I'm planning on moving my toilet from one side of my bathroom to the other. I plan to tap into an existing drain for a bathroom sink (the sink will be moved elsewhere). I'm not sure about the compatibility of the drain pipe diameters, so I guess that's the first question. If they are not...

Reducing diameter of a vent stack [ 1 Answers ]

I am replacing a shower stall in my house and found that the 3" PVC vent stack in the wall protrudes slightly beyond the studs and is in the way of where the new pre-cast shower pan will sit. I could solve the problem by using 3" to 2" reducers to narrow the vent stack pipe to 2" dia. For about 3...

Pipe diameter = poor water pressure? [ 1 Answers ]

My apartment has low pressure, especially in the shower. It's a loft building in NYC and my unit was renovated in 1985. Others in the building claim to have no issues with pressure. I'm re-doing one bath and the walls have been removed. While the pipes running to the shower area are large, the...


View more questions Search