Home > Home & Garden > Plumbing   »   Can I move a vent pipe?

 
Question Tools Search this Question Display Modes
Question
 
 
#1  
Old Mar 14, 2008, 07:11 AM
rosepetal72
New Member
rosepetal72 is offline
 
Join Date: Mar 2008
Location: Connecticut
Posts: 5
rosepetal72 See this member's comment history on his/her Profile page.
Can I move a vent pipe?

Hello everyone. I am trying to cut a window from my kitchen to my livingroom(above our kitchen sink). When I cut into the wall I noticed right in the center was a vent pipe that goes from the basement all the way to the roof. I was wondering if I can move that? Can I move this pipe?

Reply With Quote
 
     

Answers
 
 
Old Mar 14, 2008, 07:18 AM   #2  
speedball1
Plumbing Expert
speedball1 is offline
 
speedball1's Avatar
 
Join Date: Jan 2003
Location: Sarasota, Fl.
Posts: 12,679
speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.speedball1 See this member's comment history on his/her Profile page.
Pay to call speedball1 for advice ($.95/min)
Call speedball1 via Skype™
Quote:
Originally Posted by rosepetal72
Hello everyone. I am trying to cut a window from my kitchen to my livingroom(above our kitchen sink). When I cut into the wall I noticed right in the center was a vent pipe that goes from the basement all the way to the roof. I was wondering if I can move that? Can I move this pipe?
Yes you can. You may off set the vent with 45's or 90's If I knew the material of the pipe I could tell you more. Good luck, tom
  Reply With Quote
 
     
 
 
Old Mar 14, 2008, 07:18 AM   #3  
massplumber2008
Plumbing Expert
massplumber2008 is offline
 
massplumber2008's Avatar
 
Join Date: Jan 2008
Location: Boston, Massachusetts
Posts: 2,407
massplumber2008 See this member's comment history on his/her Profile page.massplumber2008 See this member's comment history on his/her Profile page.massplumber2008 See this member's comment history on his/her Profile page.
Hi rose:

There is no reason you cannot move it as long as you use the right fittings and keep the pipe the same size throughout.

I figure you want to offset this with a...90 degree fitting over, 90 degree fitting up, 90 over, 90 up and connect back onto old vent. This is ok you if you need to. The idea here, however, is that you use as few 90s to do this as possible....SO, if you can use to 45s to offset the stack (in place of 2 90s), that's great, OR if can run straight up into attic space and connect into same size vent then again...that reduces numbers of 90 degree fittings needed.

Simple fact though, in this case, 4 90 degree fittings can be used to relocate the vent.

Hope that helped...Mark

(WOW Tom....right on top of each other on that one!!)


.
  Reply With Quote
 
     
 
 
Old Mar 14, 2008, 07:24 AM   #4  
ballengerb1
Home Repair & Remodeling Expert
ballengerb1 is offline
 
Join Date: Dec 2006
Location: Wheaton, Illinois, USA
Posts: 8,123
ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.
You got it straight from two plumbers, totally moveable. Keep in mind that you will need to remove about a foot of drywall on 3 sides of the new opening , at least on one side. You need room to make your turns with what I hope is PVC. If the window is in a load bearing wall you should come back and tell us since some header work will be needed.
  Reply With Quote
 
     
 
 
Old Mar 14, 2008, 07:35 AM   #5  
rosepetal72
New Member
rosepetal72 is offline
 
Join Date: Mar 2008
Location: Connecticut
Posts: 5
rosepetal72 See this member's comment history on his/her Profile page.
Quote:
Originally Posted by speedball1
Yes you can. You may off set the vent with 45's or 90's If I knew the material of the pipe I could tell you more. Good luck, tom


Thanks for the advice--it's black pipe.
  Reply With Quote
 
     
 
 
Old Mar 14, 2008, 07:37 AM   #6  
rosepetal72
New Member
rosepetal72 is offline
 
Join Date: Mar 2008
Location: Connecticut
Posts: 5
rosepetal72 See this member's comment history on his/her Profile page.
Thanks for the help


Quote:
Originally Posted by massplumber2008
Hise rose:

There is no reason you cannot move it as long as you use the right fittings and keep the pipe the same size throughout.

I fgure you want to offset this with a...90 degree fitting over, 90 degree fitting up, 90 over, 90 up and connect back onto old vent...This is ok you if you need to. The idea here, however, is that you use as few 90s to do this as possible....SO, if you can use to 45s to offset the stack (in place of 2 90s), that's great, OR if can run straight up into attic space and connect into same size vent then again...that reduces numbers of 90 degree fittings needed.

Simple fact though, in this case, 4 90 degree fittings can be used to relocate the vent.

Hope that helped...Mark

(WOW Tom....right on top of each other on that one!!)


.
  Reply With Quote
 
     
 
 
Old Mar 14, 2008, 07:37 AM   #7  
ballengerb1
Home Repair & Remodeling Expert
ballengerb1 is offline
 
Join Date: Dec 2006
Location: Wheaton, Illinois, USA
Posts: 8,123
ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.
OK, that can be another issue. You should not cut that pipe just yet, it could be carrying some heavy load. I do not have the great pictures that Tom and Mark have but they can show you how to jack the pipe so you don't have 20' of pipe hitting you in the head.
  Reply With Quote
 
     
 
 
Old Mar 14, 2008, 07:38 AM   #8  
rosepetal72
New Member
rosepetal72 is offline
 
Join Date: Mar 2008
Location: Connecticut
Posts: 5
rosepetal72 See this member's comment history on his/her Profile page.
Thank you!

Quote:
Originally Posted by ballengerb1
You got it straight from two plumbers, totally moveable. Keep in mind that you will need to remove about a foot of drywall on 3 sides of the new opening , at least on one side. You need room to make your turns with what I hope is PVC. If the window is in a load bearing wall you should come back and tell us since some header work will be needed.
  Reply With Quote
 
     
 
 
Old Mar 14, 2008, 09:15 AM   #9  
rosepetal72
New Member
rosepetal72 is offline
 
Join Date: Mar 2008
Location: Connecticut
Posts: 5
rosepetal72 See this member's comment history on his/her Profile page.
Quote:
Originally Posted by rosepetal72
Hello everyone. I am trying to cut a window from my kitchen to my livingroom(above our kitchen sink). When I cut into the wall I noticed right in the center was a vent pipe that goes from the basement all the way to the roof. I was wondering if I can move that? Can I move this pipe?
It is a black plastic pipe about 1 to 2 inches in diameter. Sorry guys.
  Reply With Quote
 
     
 
 
Old Mar 14, 2008, 10:04 AM   #10  
ballengerb1
Home Repair & Remodeling Expert
ballengerb1 is offline
 
Join Date: Dec 2006
Location: Wheaton, Illinois, USA
Posts: 8,123
ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.ballengerb1 See this member's comment history on his/her Profile page.
ABS, you can treat that like PVC, not much weight on it. I would still clamp the pipe above the cut but this one should not hurt you like cast iron. After you make the cut at the top you know if you have any bounce in the lower pipe and can deal with that. Splice in more ABS or switch to PVC using All Purpose glue. No need to prime ABS just scuff the surfaces of both the pipe and the coupling. I'd use 4 90 degree couplings.
  Reply With Quote
 
     


Question Tools Search this Question
Search this Question:

Advanced Search
Display Modes

 
Similar Sponsors

Similar Questions
Question Asker Topic Answers Last Post
vent pipe turned into drain pipe and drain pipe into vent pipe chad278 Plumbing 3 Nov 6, 2007 06:29 PM
Move or reduce vent pipe? sucosam Plumbing 0 Aug 13, 2007 10:36 AM
vent/drain move... mtnbkr Plumbing 4 Jan 19, 2007 04:05 PM
vent pipe johnsr1 Plumbing 2 Nov 9, 2006 12:05 AM
Soil Stack Vent Pipe/Stench Pipe ( Smelly Drains ) midboy Plumbing 3 Sep 28, 2006 11:34 AM




Copyright ©2003 - 2007, Ask Me Help Desk.
All times are GMT -8. The time now is 07:44 PM.

Content Relevant URLs by vBSEO 3.0.0 RC6 © 2006, Crawlability, Inc.