    No cold water in house
    We only have warm/hot water coming from every faucet in the house. We had Mr. Plumber come out this time last year with the same problem and he said the pipes were crossed and he rerouted them. $500 later, it worked, but only for a year. So now I'm thinking that wasn't really the problem?

    My husband, who's an idiot, says it might be the heat (100+ degree days for the last month) but like I said, he's an idiot.

    I'm thinking it might be something wrong with the water heater?

    I should also mention that this problem started with the installation of a second hot water heater. We endured the no cold water problem for a couple of years before my husband would admit there was a problem that needed fixing (did I mention he's an idiot?).

    So here are my questions:

    What's causing this problem?
    Can it be fixed and if so, how?
    Can I get my money back from Mr. Plumber?

    My husband being an idiot is a problem no one can solve...
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #2

    Aug 20, 2005, 10:03 AM
    Quote Originally Posted by I want cold water
    We only have warm/hot water coming from every faucet in the house. we had Mr. Plumber come out this time last year with the same problem and he said the pipes were crossed and he rerouted them. $500 later, it worked, but only for a year. So now I'm thinking that wasn't really the problem??

    My husband, who's an idiot, says it might be the heat (100+ degree days for the last month) but like I said, he's an idiot.

    I'm thinking it might be something wrong with the water heater?

    I should also mention that this problem started with the installation of a second hot water heater. We endured the no cold water problem for a couple of years before my husband would admit there was a problem that needed fixing (did I mention he's an idiot?).

    So here are my questions:

    What's causing this problem?
    Can it be fixed and if so, how?
    Can I get my money back from Mr. Plumber?

    My husband being an idiot is a problem no one can solve ...
    I'd be interested in finding out just exactly what Mr. Plumber did to your water system to get you cold water.
    Have Mr. Idiot go out to the meter and see if you have a backflow preventer or a check valve installed. If so, yours is not a uncommon complaint.
    Back flow preventers and check valves make your water system a closed system. This means that as the water heater heats water and that water expands it has no where to go but back up the cold water pipe and into the cold water system. Water heater manufactures now recommend a expansion tank be added to the cold water supply of the heater. This allows the hot water to expand into the expansion tank instead of the cold water system.
    To check out expansion tanks click on; http://www.stateind.com/expansion/expansion.htm
    As far as Mr. Plumber's concerned , that's a done deal and a dead issue. More questions? I'm as close as a click. Tom
    I want cold water's Avatar
    I want cold water Posts: 4, Reputation: 1
    New Member
     
    #3

    Aug 20, 2005, 10:18 AM
    Sending out Mr. Idiot...
    Tom,

    Thanks for your reply! Mr. Idiot has agreed to go outside to the water meter - you do mean water meter, right? The one that would be up by the road and not anywhere near the water heater tank?

    And, because Mr. Idiot is who he is, what exactly is he looking for? Will it be obvious? Maybe I should do this myself, huh?

    Mr. Idiot's wife
    I want cold water's Avatar
    I want cold water Posts: 4, Reputation: 1
    New Member
     
    #4

    Aug 20, 2005, 11:24 AM
    Problem fixed?
    So upon doing some research on backflow preventers and check valves (b/c we didn't know what we were looking for), I found a lot of info about inground sprinkler systems. So we tried something -- we ran the inground sprinkler system which hadn't been run in over a year and then tried the cold water taps - after a while, cold water came out. It;'s not super cold, but it's not warm either.

    Does this make logical sense? Or will the house go hot again?
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #5

    Aug 20, 2005, 12:09 PM
    Quote Originally Posted by I want cold water
    So upon doing some research on backflow preventers and check valves (b/c we didn't know what we were looking for), I found a lot of info about inground sprinkler systems. So we tried something -- we ran the inground sprinkler system which hadn't been run in over a year and then tried the cold water taps - after a while, cold water came out. It;'s not super cold, but it's not warm either.

    Does this make logical sense? Or will the house go hot again?

    What you have done is to divert tepid or the warm water in your house system to the outside sprinkler system allowing cold water to enter the house system. Let it go overnight and I'll bet you have the same problem in the morning. And yes, a backflow preventer is installed next to the water meter and down stream, (ahead) of it. There is one other possibility. A crossover can occur in a single handle faucet if the cartridge's faukty but it doesn't sound like this is your problem. A simple check for the water heater would be to check the outside of the cold water supply pipe in the morning after you get up and before you draw any water. Don't flush t5he john, don't draw a glass of water, just check the pipe first. If it's hot then you have hot water backing up into your system and a expansion tank's needed. Regards, Tom
    I want cold water's Avatar
    I want cold water Posts: 4, Reputation: 1
    New Member
     
    #6

    Aug 20, 2005, 02:16 PM
    OK, we'll try that
    Thanks again, Tom!

    Although when I went to the grocery store, the idiot husband dug up the front lawn to do something with the sprinklers... sheesh. I'm sure he made it worse.

    We'll try the water heater simple test in the morning - boy, he's going to love that! Thanks so much, you are my plumbing guru!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Brand new water heater: Starts hot, then water gets cold after few seconds [ 9 Answers ]

We just moved into a brand new condo which has its own water heater. We went to take a shower this morning and the first few seconds of the shower were very hot, then it went cold after 10 seconds. We tried again after half an hour, same thing. There was enough hot water for my husband to shave but...

Hot water venting into cold water tank [ 7 Answers ]

Hello, I posted my query here a while back but unfortunately it appears to have been left to fester :confused: (query was hot water from cold water tap). After a couple more visits by a plumber, his view is that the hot water tank is overheating, venting hot water into the cold water tank at the...

No cold water in part of house.. HELP!? [ 6 Answers ]

This past Wednesday, for some unknown reason, the cold water has stopped coming out of my kitchen faucet, (on 2nd floor) as well as no cold water in going to the washer (1st floor) or the outside spigot. There is still cold water in the bathrooms on all three floors of the house (built 1991) and...

Low cold water pressure in half of house [ 1 Answers ]

I've been installing insulation under my house - there's a narrow crawlspace, so I'm sure I've knocked something about. When I got out, I had no cold water coming to our washing machine and the water pressure in the kitchen is extremely low. Here's the weird part, the hot water works in the washing...

No Cold Water In House! Please Help! [ 1 Answers ]

I am having trouble with the cold water in my house. Everything was working fine until about a week ago and now every time you turn the cold water on it goes from cool to warm in 2 or 3 seconds. I have tried letting in run, testing all of the water faucets, washing machine, etc. in the house. I am...


View more questions Search