Quote:
|
Originally Posted by tegelert Are there generally code requirements for waste line runs in regards to how far the waste line runs from the roof vent? For example, if I convert an existing bedroom into a bathroom and the toilet is say 10 feet away from the waste line roof vent, is that going to be a problem? |
Let me quote from Table 1409.3 of the Standard Plumbing Code titled "Distance of Fixture Trap from Vent",
Size of Fixture Drain Distance Trap to Vent
1 1/4" ------------------- 2 ft 6 in.
1 1/2" ------------------ 3ft. 6 in.
2" ------------------------ 5 ft 0 in.
3" ------------------------ 6 ft 0 in.
4" ------------------------ 10 ft 0.in.