    How to run a 3"drain pipe
    The relocation of my upstairs bathroom requires the change of the 3" abs drain pipe. The pipe starts at the toilet, after approx. 3 feet of horizontal run a 2" shower drain is connected with a Y-piece. Then after another 2 feet is a 1 1/2" sink drain connected with another Y pice. After 1 foot of horizontal run I want to put a 90 elbow pointing downwards. Right after this I want to put another 90 elbow going to the left side. Then there is a 5 feet horizontal run before it finally connects to the drain stack that disappears in the basement floor. Is this going to work or will I get problems at the two 90 turns? Instead of using the two 90 turns I could also use 45's. But there is still the 5 feet run before it connects to the 3" main stack. Any help woould be appreciated.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Apr 9, 2005, 04:53 PM
    I don't see a problem. Won't hurt to use the 45's, but even more important is to make them the longer radius DWV elbows. Likely that is at places like Lowe's or Home Depot stock in 3''. Verify what you have really is ABS and use cement meant for ABS with it. If you have to mix in PVC, get the cement meant for either.
    myhomereno's Avatar
    myhomereno Posts: 4, Reputation: 1
    New Member
     
    #3

    Apr 9, 2005, 06:02 PM
    I posted this question also at the "fine homebuilding" forum and the concerns were that after the two 45's the flow what not be enough to transport the solids the remaining 5 fet before it enters the 3" main stack. The sugestions were to install a cleanout on the last 5 feet run.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #4

    Apr 9, 2005, 06:49 PM
    I am not the top dog in plumbing here. If Speedball says it is OK, do it. I might point out that in some comercial building on a slab, drains run hundreds of feet horizonally just under the floor.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #5

    Apr 10, 2005, 08:50 AM
    Quote Originally Posted by myhomereno
    The relocation of my upstairs bathroom requires the change of the 3" abs drain pipe. The pipe starts at the toilet, after approx. 3 feet of horizontal run a 2" shower drain is connected with a Y-piece. Then after another 2 feet is a 1 1/2" sink drain connected with another Y pice. After 1 foot of horizontal run I want to put a 90 elbow pointing downwards. Right after this I want to put another 90 elbow going to the left side. Then there is a 5 feet horizontal run before it finally connects to the drain stack that disappears in the basement floor. Is this going to work or will I get problems at the two 90 turns? Instead of using the two 90 turns I could also use 45's. But there is still the 5 feet run before it connects to the 3" main stack. Any help woould be appreciated.

    I posted this question also at the "fine homebuilding" forum and the concerns were that after the two 45's the flow what not be enough to transport the solids the remaining 5 fet before it enters the 3" main stack. The sugestions were to install a cleanout on the last 5 feet run.
    I don't like to see "dog legs" in drainage but sometimes they're necessary. Use long sweeps to make the offset. If space is tight short sweeps are acceptable. I'm a great fan of adding cleanouts, but not when they're unnecessary. The sheer volume of water will carry the solids to the stack.
    I don't quite understand the reasoning of "Fine Homebuildings" answer. Five foot is a very short run to install a clean out on.
    If I were concerned that the layout you provided would clog up and you would have to have a "handy clean out" to keep it operating I would have given you different options. Oh well!
    Good luck, Tom
    myhomereno's Avatar
    myhomereno Posts: 4, Reputation: 1
    New Member
     
    #6

    Apr 10, 2005, 08:25 PM
    Thanks for your advice Tom.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Drain pipe leaking [ 3 Answers ]

:confused: under my kitchen I have drain pipes that run to a large pipe that goes down into ground.I have no idea what this called(sorry)where the drain pipe and this large pipeconnect is leaking.How do I repair this?

3/4" copper pipe for washer drain? [ 20 Answers ]

Parents moved into new ranch style house, and bought new washer/dryer. Drain for washer is what looks like a 1" copper stub with a 3/4" conversion fitting on it. Its about 6" off the ground. plastic bendable hose drain for washer has a rubber gasket-type fitting around it which fits in 2" PVC...

New sink drain 2" off from existing drain [ 4 Answers ]

Sorry for the dumb novice question, but thanks in advance for the advice. My new lavatory sink's drain is 2" away from lining up with the existing p- trap drain pipe. I REALLY don't want to cut off the whole p-trap drain to install a new one that would fit where I need it (as someone has...

Help me with my Drain Pipe [ 2 Answers ]

I had ceramic tile installed in an upstairs bathroom and a laundry room last week. I removed the toilet from upstairs bathroom and a washer and dryer from the laundry room on the main floor prior to installation. I put the toilet back on this week and reconnected the washer and dryer in the...

Bathroom sink wall pipe drain pipe [ 2 Answers ]

My house was built in early 70's.. No plastic.. I'm putting in a new sink and had to remove the wall pipe that goes into the wall.. I needed a longer one. It seem where it goes in behind the wall into the plumbing there was some type of gasket as pieces of it fell out when I removed the pipe.. I...


View more questions Search