    Hot water heater circuit breaker
    I have a State Select hot water heater and the circuit breaker keeps popping I can reset it and it works for about a day, any idea what may be causing the issue
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #2

    Feb 20, 2008, 06:21 PM
    Hey Cd... you don't mean the 30 amp circuit breaker to the entire heater... do you? If you do mean the 30 amp breaker... then disregard the following and let me know.. ok?

    I believe you mean that the red RESET button at the upper or lower thermostat is popping off.. you reset... pops again in a day. Here, you will need to shut the power at that 30 amp breaker... then confirm by electrical tester that no power (safety first here), (always test electrical tester on working outlet or similar to confirm that it works BEFORE trusting your life to it ;) ).

    Now, disconnect wires from the thermostat with the tripping reset button, take it to the nearest plumbing supply house (or home supply store that deals with state water heater... although any universal thermostat should work) and get it replaced. Your upper or lower thermostat is most likely defective.. Then simply replace, re-wire, and turn on power. See from there. I bet that does it.

    If I was wrong, like I said let me know and we will see from there. BUT the thermostats trip once in awhile... usually because simply gone defective.

    Hey, if my answer helped, please RATE THIS ANSWER by clicking on rate this answer button at upper right or bottom of this post. Thank you.
    Cdaddy54's Avatar
    Cdaddy54 Posts: 2, Reputation: 1
    New Member
     
    #3

    Feb 21, 2008, 06:03 AM
    Quote Originally Posted by Cdaddy54
    I have a State Select hot water heater and the circuit breaker keeps popping I can reset it and it works for about a day, any idea what may be causing the issue
    Thanks Mass! You're right. I meant the reset. I will follow your advise and let you know the out come.
    mcook65's Avatar
    mcook65 Posts: 1, Reputation: 1
    New Member
     
    #4

    Nov 10, 2012, 06:28 PM
    Thank you for the question and answer. I have a 2005 water heater that just recently started to heat the water way to hot so I turned down the temperature and the water is still super hot, do you think it's the thermostat.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #5

    Nov 10, 2012, 07:48 PM
    Hi Mcook65

    Yeah, certainly sounds like the thermostat(s). I would recommend changing both the upper and lower thermostats at this point... super cheap and quick to change both out! That should resolve your issue!

    Mark

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Theory of vacuum Circuit Breaker & sf6 circuit breaker [ 15 Answers ]

I want to know about the basic Theory of vacuum Circuit Breaker & sf6 circuit breaker

New hot water heater installed, but no hot water pressure. Plenty of cold water? [ 11 Answers ]

Hi, I own a small plumbing service and have a problem I've never encountered before. I installed a new top vented gas water heater for a customer. Turned the main back on, bled air out of the lines, etc. Problem is there is no hot water pressure throughout the house. Cold water pressure is fine....

Connecting a tankless water heater and separate hot water heater [ 6 Answers ]

What I have is this. An oil fired boiler that generates hot water for my house baseboard heating system. Contained within the boiler is a tankless heater that is heated by way of the firebox in the boiler. The tankless heater is used only for domestic hot water. It has a separate CW supply to the...

Hot tub circuit breaker tripping [ 1 Answers ]

I have had this hot tub for about 6 years. It has a history of blowing an internal 20 amp fuze. But, lately it runs a little while and then trips the circuit breaker. Any ideas?

No hot water - hot water heater and cold working [ 1 Answers ]

HELP! Its freezing out and we have NO hot water! Cold is working fine everywhere - but nothing comes out of the hot side anywhere. The hot water heater appears to be working? Did the hot water pipes freeze? Why the hot side and not the cold? Please help.


View more questions Search