Quote:
|
Originally Posted by funfamilyfare I used a CPVC female threaded fitting with ears on it to fasten to the wall stud. I then screwed a 4" brass nipple to it with teflon tape and attached the valve to the other end with teflon tape as before. I now notice a slight weeping or sweating leak at the CPVC fitting. |
Using metallic threaded fittings on plastic female fittings is just asking for trouble, particularly on the hot side of the system.
Expansion and contraction within the system will eventually crack the female fitting.
If you want to make a proper plastic/metallic transition, then you should use an approved
brass to CPVC drop ear 90.