| Hold the phone!! If the drawing reflects what's under the slab then you're in deep doo-doo.
First off, as Doug pointed out, you are discharging a major fixture mast a unvented minor one and you can't do that.
Second, yiou have combined the fixture vent with the dedicated ejector pit vent. Dedicated means just that. The pit vent MUST be separate from the house system.
Thirdly, The loop that you've placed the X on is unnecessary. The vanity can drain into either of the raisers shown.
Sorry I couldn't be more supportive. Regards, Tom |