ABS/PVC Pipe Connections

Asked Aug 14, 2006, 05:47 PM — 7 Answers
I am about to do a modest bathroom remodel on a 40 year old house. The existing DWV piping is black plastic ABS pipe. I want to use the white PVC but I read somewhere that you should not join the two different pipe types directly. Is this accurate? If so, what is the easiest method. The only other couplings I have seen in the Home Depot are those rubber fittings with metal clamps.


Thanks in advance

7 Answers
speedball1's Avatar
speedball1 Posts: 27,664, Reputation: 9541
Senior Plumbing Expert
 
#2

Aug 14, 2006, 08:05 PM


Comingling ABS and PVC became much more permeate with Oatey All Purpose Cement. All you need is Primer, Oatey Cement and a coupling of either ABS or PVC. Good luck, Tom
Helpful
mountainlio7's Avatar
mountainlio7 Posts: 4, Reputation: 1
New Member
 
#3

Feb 17, 2010, 03:38 PM
In 2001, we purchased a manufactured home which has the sewer abs black. Our septic was PVC white. We paid over $300 and had a inspection which passed. They installed a rubber coupling. All fine and dandy until a week ago Feb 2010 we smelled something funny and discovered the black ABS pipe fell out of the rubber coupling and sewage all under our house! I read where if I ever went to sell it that sometimes it has to pass inspection. I studied it and this is what I ended up doing LOL
I took that rubber coupling crap and threw it away. I drained all the sewage. I purchased a white male end screw in type fitting and glued it to the septic/white pvc side using proper glue. I then got a female black ABS end and screwed it into the white side! There you go and if that doesn't pass who cares because I will not clean up sewage again. Now I have to purchase some lime to clean up the smell .


My recommendations is join them using a male end black/white and a female end black/white. If that does not work they do make a glue green in color that is compatible glueing the two abs and PVC together. I chose the male/female screw into each other method.
Helpful
speedball1's Avatar
speedball1 Posts: 27,664, Reputation: 9541
Senior Plumbing Expert
 
#4

Feb 17, 2010, 04:09 PM


Mountain,
You are responding to a 4 year old thread that's dead. Please look in the upper left hand corner for the date. Thanks, Tom
Helpful
mountainlio7's Avatar
mountainlio7 Posts: 4, Reputation: 1
New Member
 
#5

Feb 17, 2010, 04:43 PM
I am sorry speedball1. When one pays $300 and passed inspection then finds a huge puddle of sewage under there house well lets just say I did not even notice the date of this thread until you mentioned LOL
Helpful
Milo Dolezal's Avatar
Milo Dolezal Posts: 5,880, Reputation: 1933
Plumbing Expert
 
#6

Feb 17, 2010, 07:16 PM


Moiuntain, Fernco couplings are designed to connect PVC and ABS pipes. If your coupling slipped it was because it wasn't properly installed, tighted with tension pre-set wrench and tested when originally installed. Also, each end of the pipe has to be inserted into the coupling all the way with only 1/8" separation between those two.

Such a connection with Fernco coupling becomes weak point in the pipe. To prevent pipe separation pipes have to be properly supported. If installed properly - it will last as long as rest of the plumbing in your house.
Helpful
mountainlio7's Avatar
mountainlio7 Posts: 4, Reputation: 1
New Member
 
#7

Feb 19, 2010, 11:41 AM
Thank you Milo Dolezal. The installation which was installed in 2001 was not tested. The Fernco coupling rubber was still in very good shape. The problem was the top band was not tightened to proper tension and the installer only put two inches of black pipe in the Fernco coupling. With only two inches placed into the Fernco Coupling and the band not tightened to proper specs is the reason it failed. The rubber of the Fernco coupling was in very good shape. Like the day they purchased it. I couldn't believe it passed inspection!
Helpful
mountainlio7's Avatar
mountainlio7 Posts: 4, Reputation: 1
New Member
 
#8

Feb 19, 2010, 11:44 AM
Quote:
Originally Posted by Milo Dolezal View Post
Moiuntain, Fernco couplings are designed to connect PVC and ABS pipes. If your coupling slipped it was because it wasn't properly installed, tighted with tension pre-set wrench and tested when originally installed. Also, each end of the pipe has to be inserted into the coupling all the way with only 1/8" separation between those two.

Such a connection with Fernco coupling becomes weak point in the pipe. To prevent pipe separation pipes have to be properly supported. If installed properly - it will last as long as rest of the plumbing in your house.
Exactly Milo it was operator error. Top band not tightened and only two inches of black ABS pipe inside the Fernco coupling. I estimaged approx black ABS pipe was 4 inches away from the PVC pipe.
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

Music Connections [ 1 Answers ]

I really, really, like the bands Jack's Mannequin and Diffuser. Could someone give me a list of similar artist. Thanks, Josh

Network connections [ 2 Answers ]

Hi I have a good feeling that when I play an online game such as age of empires or fifa 06 etc the other computers on my network don't work, the internet we share seems to get unconnected for them. I'm not sure if this is why, but it only seems to happen when I'm playing a game does anyone have any...

Help with shower connections - PVC to cast [ 1 Answers ]

Hi all - I am replacing a tub / shower in an antique home, with a new one piece shower (60 x 30). I need to connect the drain assembly to existing PVC which is connected to Cast. The problem is the PVC / Cast connection is loose (about 2 feet from the where the shower would drain). The cast...

Plastic and Copper pipe connections [ 1 Answers ]

Help.... I am trying to replace a kitchen faucet. The copper water supply pipe is connected to a plastic shut-off valve. I want to replace the plastic shut-off valve with a metal valve. The plastic shut-off valve will not come off the copper water supply pipe. How do I get this off? I tried...

Valve connections [ 1 Answers ]

Tom, do you prefer a threaded valve connection or a soulder joint? Is it recomended to remove the guts of the valve before welding joint? What is the terminoligy for valve connections? I have decided on a Moentrol valve with built in 3 way diverter so I can have a hand shower and body sprays. They...


View more Plumbing questions Search