Home > Home & Garden > Heating & Air Conditioning   »   York turn on sequence sometimes wrong

Question
 
 
#1  
Old Nov 11, 2009, 09:02 AM
mtngrwn
New Member
mtngrwn is offline
 
Join Date: Nov 2009
Posts: 4
mtngrwn See this member's comment history on his/her Profile page.
York turn on sequence sometimes wrong

I have a York P2MPD14N08001B furnace that occasionally does not follow correct power up sequence, the end result is that it blows cold air with burners off. When it does not work correctly, the blower turns on right away. The glow plug ignitor tries to heat up, but then cuts off shortly thereafter. The gas never turns on, and the blower will continue forever until furnace is reset. Initially a single reset will clear it out, but the problem seems to get worse as time goes on. Furnace repairman replaced pressure switch last year, and said if that does not fix it then the control board must be at fault. Once he replaced that(middle of winter), it worked great for a couple weeks, and then the fault came back, increasingly as time went on. At the end of last winter, 1 reset out of 20 would finally get the furnace to follow the correct sequence. After being off all summer, it worked perfectly for about 2 weeks. And now it is repeating the fault more and more often again. The fault LED has been broken off by some repairman along the way, so that diagnostic tool is unavailable.

Sorry for the wordiness, but any help would be appreciated! I could get the board and replace by myself, but am trying to avoid wasting $200 if that is not the problem.

Thanks!

Reply With Quote
 
     

Answers
 
 
Old Nov 11, 2009, 12:03 PM   #2  
New Member
mtngrwn is offline
 
Join Date: Nov 2009
Posts: 4
mtngrwn See this member's comment history on his/her Profile page.
To clarify, the repair replaced the pressure switch only, not the control board. Furnace has original control board as far as I know.
  Reply With Quote
 
     
 
 
Old Nov 11, 2009, 01:56 PM   #3  
Ultra Member
Joshdta is offline
 
Joshdta's Avatar
 
Join Date: Apr 2009
Location: West Virginia
Posts: 1,677
Joshdta See this member's comment history on his/her Profile page.
Send a message via AIM to Joshdta
sounds like a control board problem to me.
  Reply With Quote
 
     
 
 
Old Nov 11, 2009, 02:23 PM   #4  
Ultra Member
KC13 is offline
 
KC13's Avatar
 
Join Date: Aug 2007
Location: Cincinnati, Ohio
Posts: 2,447
KC13 See this member's comment history on his/her Profile page.
I'm starting to sound like a broken record...have you tried bypassing the thermostat? Connect "R" and "W" wires directly together and report result observed.
  Reply With Quote
 
     
 
 
Old Nov 11, 2009, 04:30 PM   #5  
New Member
mtngrwn is offline
 
Join Date: Nov 2009
Posts: 4
mtngrwn See this member's comment history on his/her Profile page.
Should I connect the wires together when it cycles up incorrectly? Right now, it only cycles up incorrectly about 3 times a day, but it is increasing from 2 weeks ago when it ran perfectly at all times.

I've went through 2 programmable tstats and am on the most basic non-programmable unit that Honeywell makes, I believe eliminating the tstat as the source of the problem.

I work with electronics, and I can tell you the control board was sloppily made. Component leads were touching each other under the conformal coating. Even so, it worked for 10 years before I started seeing problems. The age of the furnace is 14 years I think.
  Reply With Quote
 
     
 
 
Old Nov 12, 2009, 02:02 AM   #6  
Ultra Member
KC13 is offline
 
KC13's Avatar
 
Join Date: Aug 2007
Location: Cincinnati, Ohio
Posts: 2,447
KC13 See this member's comment history on his/her Profile page.
Quote:
Originally Posted by Joshdta View Post
sounds like a control board problem to me.
Indeed, most functions are timed, and old resistors...just can't put up a fight like when they were younger...members of 'the Resistance'...
  Reply With Quote
 
     
 
 
Old Nov 12, 2009, 03:54 AM   #7  
New Member
mtngrwn is offline
 
Join Date: Nov 2009
Posts: 4
mtngrwn See this member's comment history on his/her Profile page.
I don't suppose there is anywhere I can find a schematic for the control board? I did an internet search and couldn't find it with the p/n on the board. Unless it's the PROM IC on the board, I could probably fix it with the schematic. Johnson Controls is the manufacturer of the board.

Thanks for your input guys...
  Reply With Quote
 
     

Answer this question

Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes
Ask your question or search...

 




Similar Threads
My other computer will not turn on,it keeps saying somthing is wrong with it
(2 replies)
Wrong Thermostat or Compatability Issue W/York ac/heat pump and Janitrol Condenser
(0 replies)
What is Wrong, York H&A Unit Frosting/Freezing?
(3 replies)
furnace turn on sequence
(2 replies)
faucets turn the wrong way
(2 replies)


Bookmarks and Sharing
bookmark twitter facebook

Thread Tools
Show Printable Version Show Printable Version
Email this Page Email this Page
Search this Thread

Advanced Search




Copyright ©2003 - 2010 - Advizo, LLC
All times are GMT -8. The time now is 09:51 AM.