    York Diamond 80 not lighting completely
    Hello,
    I have a York Diamond 80 furnace that was installed new in 2001. My problem is that the Heat exchanger will not fully light and stay on. The ignitor works fine but when ignition begins only the two burners closest to the ignitor ignites. The two will burn for a few seconds then go out. I can't figure out why all the other burners don't ignite when the 1st two do.
    If I remove the front panel they will all light up, always it seems. Why? Is there not enough air getting in there with the door panel on. Also I noticed the if I blow on the two ignited burners all the others will light up. Once they all light up the furnace seems work okay until it comes time to cycle on again.
    I have replaced the temp sensor and think the igniter is probably okay since it does ignite the two burners closetes to it. Why would the fire not spread to all the other burners unless I blow air around them or remove the door panel? Why do I always get the weird ones?
    Thanks for any help anyone can provide. I have had techs out here over the last few years that can't seem to permanently figure this out.
    Do I need to buy a new furnace?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Oct 13, 2009, 02:22 PM
    You do not need a new furnace but you do need to find a service person that knows exactly what they are doing to correct this situation. The furnace needs to be serviced and at that time the service person will have the proper tools to set and adjust the burner if necessary. The reason I say this is because the burners are not jumping across so they all light at the same time and that is not good.
    gwsheets's Avatar
    gwsheets Posts: 3, Reputation: 1
    New Member
     
    #3

    Oct 13, 2009, 02:30 PM

    Thanks but you didn't provide any possible solutions beyound what I have tried. Have it looked at by a professional...
    The installer was/ is pretty reputable, he is the one I have had out servicing the furnace since new. He thinks there may be some inherent problem with the heat exchanger.
    What may be the top 3-4 reasons that my be causing this? Anyone?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Oct 13, 2009, 02:48 PM
    There could be many different reasons and I did not list them since I felt you may not have the tools or knowledge to do the testing.
    If you have a manometer check the discharge gas pressure and make sure it is within spec for starters. They look like these below.

    Then with that done you might pull all burners and clean the heat exchanger/burner tubes/etc. Pay attention to any jumpers on the burners that might be bent/dirty/or rusted and replace if necessary.

    NOTE if the person that has been servicing your unit since new fells that there is a heat exchanger problem why did he not test it?

    Post back with results of your work.
    Attached Images
      
    gwsheets's Avatar
    gwsheets Posts: 3, Reputation: 1
    New Member
     
    #5

    Nov 15, 2009, 09:34 AM

    Well I finally figured things out and fixed the problem with is York POS
    I replaced it with a new Lennox.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

YORK DIAMOND 80 Not Staying Lit. = No Heat blowing. [ 8 Answers ]

Hey you I have a York Diamond 80 - I don't have furnace model no. but I do have the Johnson Control board's model no. G91G951ADB-1403 (part no 031-01234-000). The problem: When I try to run the furnace the combustion blower, glow coil, and the 5 ports (burners) function. However the burners...

York Diamond 80 blowing cold air. [ 13 Answers ]

Hi All... Hopefully uou can help me out... I have a york diamond 80 gas furnace. It was working fine up until a few days ago.. It began to blow out cold air when the house clearly was not even close to "requested" temp. It turns on, starts the initial motor, the humidifer also kicks...

York Diamond 80 With New Control Board [ 9 Answers ]

Hello. I have a York Diamond 80 furnace with a new Emerson S1-33109167000 control board. The problem began when the fan wouldn't turn off even though the A/C compressor had turned off. The original control board had gone bad and was replaced. But, the fan still keeps on running. The led has a...

Diamond 80 York Leaks Water [ 5 Answers ]

My Diamond 80 York central heat and air unit is leaking water under the carpet of the room where the unit is housed. It has saturated the carper in the front of the door to this room. Had repair person come out and he first told me it was the coil and that it was around $700 to replace a coil. ...

York Diamond 90 [ 1 Answers ]

I have a york diamond 90 and I have 4 code show what could it be


View more questions Search