    cbecker111's Avatar
    cbecker111 Posts: 9, Reputation: 1
    New Member
     
    #1

    Nov 30, 2008, 06:10 PM
    White rodgers 50a50-241 7 flash error code>>>
    I have a York Furnace natural gas with a white rodgers 50a50-241 board,
    After no heat just blowing cold air I shut off the system let it sit for about 5 minutes and turned back on... worked fine for 3 days. Now it give me 7 flashes from the board after 3 tries at lighting on its own. Ignitor burns hot gas supply seems to click and go on but about 5-8 seconds after gas goes on ignitor turns off. The seven flashes mean lockout due to no ignition... what is the fix??
    Thanks for your time
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Nov 30, 2008, 06:17 PM
    Quote Originally Posted by cbecker111 View Post
    I have a York Furnace natural gas with a white rodgers 50a50-241 board,
    After no heat just blowing cold air I shut off the system let it sit for about 5 minutes and turned back on...worked fine for 3 days. Now it give me 7 flashes from the board after 3 trys at lighting on its own. ignitor burns hot gas supply seems to click and go on but about 5-8 seconds after gas goes on ignitor turns off. The seven flashes mean lockout due to no ignition...what is the fix???
    Thanks for your time
    Manual

    http://www.white-rodgers.com/wrdhom/...pg0259_264.pdf

    If you have a flame sensor on that unit clean it.
    Attached Images
     
    cbecker111's Avatar
    cbecker111 Posts: 9, Reputation: 1
    New Member
     
    #3

    Nov 30, 2008, 06:23 PM

    Thanks, I will try that but I seem to remember that I replaced it about 3 years ago and it still looks fine.
    Thanks god for fireplaces and space heaters.
    Thanks for any other answers about a solid parts fix if it needs it.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Nov 30, 2008, 06:26 PM
    I replaced it about 3 years ago and it still looks fine


    Looks are deceiving.
    cbecker111's Avatar
    cbecker111 Posts: 9, Reputation: 1
    New Member
     
    #5

    Nov 30, 2008, 06:27 PM

    I will go back home and take it out!

    Thanks
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #6

    Nov 30, 2008, 06:50 PM
    Sand paper works well. Do not touch the ignitor they are sensitive in nature.
    cbecker111's Avatar
    cbecker111 Posts: 9, Reputation: 1
    New Member
     
    #7

    Nov 30, 2008, 07:48 PM

    It has been about an hour and it seems to have worked.
    The sensor didn't seem to be that covered in anything... not saying it didn't work but it says on one of the lad flash error decals that the lockout will end after an hour>>> might that be why it worked and if so could I still have a problem later?
    Not questioning your ability... just wanting to cover all bases and make it right before we leave for 5 days from the frozen midwest and don't need to come back to a set of frozen dogs and house.
    Thanks
    cbecker111's Avatar
    cbecker111 Posts: 9, Reputation: 1
    New Member
     
    #8

    Nov 30, 2008, 10:08 PM

    So it didn't work.
    After it hit the set temp on the thermostat it did the same thing again... 7 flashes and the fan blowing cold air!
    Got any ideas anyone?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #9

    Nov 30, 2008, 11:03 PM
    7 FLASH:This fault code indicates that flame could not be
    established. This no-light condition occurred 3 times during
    the call for heat before locking out. This may be caused by
    low gas pressure, faulty gas valve, faulty hot surface igniter
    or burner problem.
    This is from a York service manual. You did not supply the exact model number of your unit just the circuit board number but all units with this board will be the same.

    Her is the manual

    http://johnsonsupply.com/york2001/PUB/N4u.pdf

    Service people usually have meters to use to test the parts of the ignition control system. Without a meter it is a parts replacing game since more than one part can be the problem. I told you to clean the sensor since that was the cheapest way to go first.
    The directions for testing are in the above manual for a unit that uses the control board you have. If you have the means to test by all means do if not you will be replacing partys and hope for the best.
    BTW other than this happening have you performed any service work on the furnace lately. The reason for the question is this circuit board is sensitive to reversed polarity and you will see a message in the manual also. It is a good manual with all the specs for testing included. If you have a meter and know how to use it then you should be able to find exactly what part is at fault. Since I am not there I can not do this testing for you.
    cbecker111's Avatar
    cbecker111 Posts: 9, Reputation: 1
    New Member
     
    #10

    Dec 1, 2008, 11:31 AM

    Wow Thanks for the PDF!
    That is my furnace.
    I got up at 2 am to start er up and got the house warm.
    I called a service guy that had taken care of my shop stuff. He came out and checked the water drain from the combustion air fan... had a lot in the hose. He thought too much water would have caused the fan to overheat and slow not letting the pressure switch to work. He restarted the system, which has been working all morning... and after putting the drain hose back in he touched the small combustion air motor and was very hot, I also touched it. He turned off the main switch and turned it back on about 3 times in a couple minutes the system lite each time but the combustion motor was hot and got a little cooler but then got hot again while running and he thinks it overheated for a split second and when it did shut the system off.
    I did see the system shut down just before he left and it seem to click like the combution fan turned off for a second but turned right back on. I am betting it should not even be warm?? So I think that is the issue.
    I have NOT done any service that woulkd have disconected any power or wires.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #11

    Dec 1, 2008, 11:39 AM
    Lucky guess on the manual. LOL. When you post it is always good to give as many brands and model numbers as possible since we can then look up items of interest that might be causing the problem.

    Water retention in the hose can cause problems and if the motor ran long enough it could have damaged it. The combustion fan should not be running unless the thermostat is calling for heat and the furnace is in operation. Sounds like you have a handle on the situation.

    Glad you have it running since winter is here. If the service person recommends the motor/combustion blower needs to be replaced I would do that and make sure the reason is found for the water accumulation. Things do plug up now and then.
    cbecker111's Avatar
    cbecker111 Posts: 9, Reputation: 1
    New Member
     
    #12

    Dec 1, 2008, 12:22 PM

    Thanks for your help!
    Do you have a paypal account?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #13

    Dec 1, 2008, 12:44 PM
    I do have a Pay Pal account BUT I accept NO money for my services. Here is what you can do for both of us if you like. During the Holiday season there are many food pantrys and things of that nature that accept donations so a donation to one of your choice would work well. Lets face it both you and I are doing OK but there are many others especially now that are not. Your donation no matter what size will help someone help themselves.

    Glad you got it fixed and may the Holiday spirit burn brite for you every year.
    cbecker111's Avatar
    cbecker111 Posts: 9, Reputation: 1
    New Member
     
    #14

    Dec 1, 2008, 01:30 PM
    I think the combustion fan has been replaced once already...
    Got a parts list for a york P2LND12N07501A?
    The fan is a Fasco Ind 22H59254
    Can't find it...
    We do have a local food bank and I will make a donation. We generally support one statewide charity but have no problem donating were you want.
    Thanks
    Chris
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #15

    Dec 1, 2008, 02:11 PM
    If that is a fasco number it is a private list number for york and all the Johnson control furnaces manufactured under many different names. Luxair,Coleman etc.

    I am seeing this number. It is aYork part number BUT I would not trust it

    373-20717-001 complete venter.

    Can you get the Exact model number off your unit?

    If so I can try to get a Exact part number for you I believe since I have a electronic parts catalogue for those companys but it has to have a Exact furnace model to work.

    Or sometimes you can get a good deal on Ebay but the numbers have to match see example.

    FASCO COLEMAN GAS FURNACE DRAFT INDUCER ELECTRIC MOTOR - eBay (item 330289436796 end time Dec-01-08 19:13:13 PST)

    This one is marked for a Coleman but that is one of the companys that also is unser York or Unitary Products group UPG for short. This is just a example
    cbecker111's Avatar
    cbecker111 Posts: 9, Reputation: 1
    New Member
     
    #16

    Dec 1, 2008, 03:55 PM
    The York ttmodel I gave is correct...
    The fasco model is 70624435 I missed it the first time...
    Got a good place to buy them...
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #17

    Dec 2, 2008, 02:44 AM
    According to the Fasco number you supplied this is the only link showing that part Number.

    115 Volt Furnace Inducer Blower Motor (Coleman, York, Moncrief ): American HVAC Parts


    These part numbers from the electronic Cat.
    York old part number

    373-14249-001

    York new part number

    324-25960-000

    Patriot Supply - 324-25960-000


    York Inducer Motor Part #S1-324-25960-000


    324-25960-000 York Draft Inducer Assembly. [324-25960-000] - $210.00 : K & L Supply, Inc. (219) 874-6560, Where one call (or click) does it all!!!






    UTL Ebay.
    Ize's Avatar
    Ize Posts: 1, Reputation: 1
    New Member
     
    #18

    Jan 4, 2010, 06:15 PM
    hvac1000,

    Just wanted to thank you for your post on this. I've had the same unit serviced for the same problem the last 3 years. 1st year my fault, second, not quite sure, and then last January again. They replaced the limit switch with a higher temp unit, and it ran fine the rest of the winter and into this fall.

    Until a month ago of course. Same problem. So I really started researching it and it had settled down until the last day or so. I cleaned the sensor like you suggested, now I'm keeping an eye on it.

    Just wanted to say thanks! Hope the Holidays were good, and the New Year is great for you.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #19

    Jan 4, 2010, 06:43 PM
    Thank you for the kind words and I hope you have the same.
    Mike242424's Avatar
    Mike242424 Posts: 1, Reputation: 1
    New Member
     
    #20

    Oct 13, 2012, 12:16 PM
    My gas would turn on for four seconds then off then on again for four for seconds then stay off for two minutes and then the same thing I cleaned the flame sensor on the unit with sand paper as suggested above and it worked! Thanks very much!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

How do I find a wiring diagram for White Rodgers 50A50-241 [ 1 Answers ]

I nedd to find a web site that I can download a wiring diagram for a York AC & heating unit with a White Rodgers 50A50-241 Thanks, Paul:rolleyes:

White Rodgers 50A50 - 241 [ 1 Answers ]

My heater isn't blowing warm air. It doesn't appear to be igniting. What is the normal voltage output of the igniter wire?

White rodgers 90-113 [ 2 Answers ]

How to wire a relay

White-Rodgers 50A50 -288 Wiring [ 1 Answers ]

I have a white-rodgers controller for my furnace/airconditioner, it has a white-rodgers mercury thermostat. Is there a wiring diagram I can follow to re-connect the thermostat? Does it also show where to terminate the coil wires for my condenser? Thank you Todd


View more questions Search