Quote:
|
Originally Posted by kajora In May when I first turned on my ac I had wet spot on my basement floor that came through my carpet. I had to put a condensate pump on near my furnace and water heater. That seemed to solve the problem until yesterday I noticed that the same spot as before is wet again and also around my furnace. What do I need to do? |
In my area we run our AC condensate lines out of 3/4" PVC and terminate them outside the house to drip on the ground. It's illegal to connect condensate lines, storm drains or roof leaders to a sewer line. AC condensate lines grow a kind of jelly in them and stop up. When that happens we clear the line out by shooting compressed air through the line and then closing off the end, filling the line up with bleach and letting it set for a few hours and then blowing it out again. Hope this helps with your problem. Good luck, Tom