Water Rushing through baseboard heat pipes

Asked Dec 28, 2006, 12:53 PM — 4 Answers
We have a Weil Mclain Gold Oil furnace that is approximately four years. The furnace generates heat through our hotwater baseboard heat pipes. Lately we hear the sound of rushing water in the pipes. In the past we have heard banging when the system is cold and heating up, but this is something new.

Any idea what this is and how to fix it?

Thanks

4 Answers
Morrowrj's Avatar
Morrowrj Posts: 331, Reputation: 104
Full Member
 
#2

Dec 28, 2006, 02:53 PM
Both banging and "rushing water" sounds are signs of air in your lines. Depending on the system, you may have small bleeder valves at the ends of your radiators. These are opened, generaly with a small key and the air is bled out until just water is present. If there are no bleeder valves present you may have an air removal system at the boiler. This is usually found directly above a small tank (about 12") These are meant to be automatic, but can sometimes get plugged with sediment or other debris. Check the top of this device for an air valve like you would find on your car tire and make sure it operates freely.




Good luck
Helpful  (1)
helpforhome's Avatar
helpforhome Posts: 1, Reputation: 1
New Member
 
#3

Jan 8, 2010, 08:35 PM
This has been the most simple and best answer I have come across for the problem with banging and running water in your baseboard heating pipes! Thank-You Morrowrj!
Helpful
Kmayher's Avatar
Kmayher Posts: 1, Reputation: 10
Junior Member
 
#4

Nov 21, 2010, 07:57 PM
Thank you so much! It's 11pm and we were just awakened by the same noises in our radiator... Your answer quickly led us to fixing the problem!
Helpful
RakaNJ's Avatar
RakaNJ Posts: 1, Reputation: 10
Junior Member
 
#5

Mar 2, 2012, 02:14 AM
someone know if that situation increase the bill?
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

Electric Baseboard Heat ?'s [ 7 Answers ]

Hi All, I have electric baseboard heat in our home, and each room is controlled separately. And this may sound dumb..... Do I need to have the heat set at a certain minimum temperature for the winter? (we live in MN) Also, is it more cost efficient for me keep them in each room on at a...

Constant 'rushing water' noise in pipes! [ 2 Answers ]

Help! Over the last month, we have had a constant rushing water noise in our pipes, both upstairs in the toilet and downstairs at the kitchen sink (both appliances on the mains). We thought the water board had changed their pressures but they haven't. We noticed that out neightbours drive way...

Baseboard electric heat [ 1 Answers ]

Does anyone have any recomendations for brands/style of baseboard heaters? Have looked at hydrosil, they claim to be efficient but are higher priced units. Are the fluid/gel filled units that much more efficient than the cheaper units? Thanks

Baseboard heat question [ 12 Answers ]

I've roughed in wiring to install 2 baseboard heaters in a room in my basement.I want to make sure that I got it right.I ran 12/2 wire from the panel to the wall thermostat box,then a separate 12/2 line out to each heater location.I want to use one 1000w heater and one 1500w heater and put them on...

Thermostats for baseboard heat [ 4 Answers ]

We built our house 30 years ago using electric baseboard heat. This is 240 volt electric heat. We would like to change the original thermostats (Mears M7) to progammable digital themostats. Those that we have looked at indicate two models; single pole and double pole. How would I determine which...


View more Heating & Air Conditioning questions Search