    Trane furnace troubleshooting - XV90 error code?
    My XV90 upflow furnace gives a 9 red flash code when it starts up. My installers guide says it is an "Open Inducer Limit switcch". The furnace works OK, should I be worried about this?
  • Jan 23, 2010, 05:26 PM
    T-Top

    Only be worried if he bypasses the limit switch.
  • Jan 31, 2010, 09:08 AM
    moe882
    Our 3 yr old xv90 gave off the same code when it stopped overnight. Had a repairman out who quickly saw that the tube that expels the water was frozen at the tip, causing the unit to shut down. A quick blow-torched screwdriver head inserted into the tip tapped the hole and everything started up and ran perfectly.
  • Feb 19, 2011, 04:22 PM
    Jamesbill
    Anybody have a four red flash error code. Replaced the temperature limit switch. Not getting any codes,but the gas furnace still shuts off after a few minutes and. Thermostat shows desired temp five degree warmer than room
  • Oct 11, 2011, 12:57 PM
    Steveywags
    How do u open limit switch?