    Thermostat Replacement Honeywell 890121 - Hunter 44110
    Hi there! Need help to replace an old Honeywell model 890121 with a Hunter 44110

    My existing (Honeywell 890121) wiring:
    Brown - C
    Green - G
    Yellow - Y --jumpered to--W
    Red - R
    White - O

    Hunter 44110:
    G
    RC--jumpered to--RH
    Y
    W

    Not sure which one goes to where...

    Thanks!
    letmetellu's Avatar
    letmetellu Posts: 3,151, Reputation: 317
    Ultra Member
     
    #2

    Jan 7, 2007, 09:31 PM
    The normal wiring would be.

    Red wire to the RC RH terminals... this it the power coming from the transformer.

    The white wire goes to the W terminal... this is returning the power back to the gas valve.

    The Green wire goes to the G terminal... this is returning the power to the blower relay.

    The yellow wire goes to the Y terminal... this is returning the power to the condensing unit.

    Unless the new thermostat needs 24 volts to operate and it is a battery operated thermostat the brown wire is not needed... it is the other side of the power coming from the transformer.

    All of this information depends on how your wires are connected to the terminal strip at the furnace. But they should be connected the same at the terminals there. With one exception, the yellow wire should be connected to the Y terminal with one of the wires going to the condensing unit, the other wire from the condensing unit should be connected to the C terminal, which is the common.
    Ping's Avatar
    Ping Posts: 2, Reputation: 1
    New Member
     
    #3

    Jan 7, 2007, 11:21 PM
    Thank you very much "letmetellu".

    That's all I need to know... appreciate it.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Help to replace thermostat Honeywell T841a for Hunter 44155c [ 1 Answers ]

Hi, I am trying to replace my T841a 1712 Non-Programmable Heat Pump Universal Thermostat for a Hunter Model 44155C, but I can't make the new unit work.:confused: The Honeywell thermostat has the following connections: Color Cable Terminal Blue -----> X Red -----> W2 ...

Hunter 44110 Programmable Thermostat Wiring HELP! [ 3 Answers ]

My current thermostat has the following six wires, hooked as follows: Orange to O Green to G Yellow to Y1 Red to R Black to C White to W1 I am attempting to install the Hunter Programmable thermostat, which only gives me 5 placements for wires:

Wiring question replacing Honeywell thermostat w/Hunter [ 0 Answers ]

I am replacing an old standard Honeywell thermostat (model T8034C) with a Hunter programmable digital model 44110. I have a 5-wire system. The wires are color coded and the Honeywell labels match the wire colors. Those are: White, Yellow, Green, Orange, and Red. THe only labels on the...

Wiring a replacement Honeywell Thermostat [ 1 Answers ]

I purchased a Honeywell Vision 5-1-1 Day programmable thermostat to replace a Lennox thermostat (51H4301). This is an all electric heat pump type unit (Lennox HP 21-511-5P). According to the Honeywell manual, if the old thermostat has wires W1, Y1 and W2, some system modification is required. Call...

Hunter vs. Honeywell [ 1 Answers ]

Just purchased a new house that has two heating/cooling systems. I need to install programmable thermostats. Comparing Hunter to Honeywell, which one is the better company to go with?


View more questions Search