    Thermostat Q - Blower Does Not Turn ON in FAN Auto Mode
    I just installed a NOMA 7-day programmable thermostat for an electric furnace/AC system (ceiling unit). I believe the wiring (5-wire) is correct.

    When I set it to COOL with Fan set to AUTO, it turns on the A/C and the fan automatically. Good.

    But when I set it to HEAT with Fan set to AUTO, it turns on the heating system but the fan doesn't. The fan does turn on when I force it by setting the switch to ON.

    Any idea why?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Oct 18, 2006, 09:47 AM
    The heating mode uses a different winding in the fan motor controlled by a different relay than cooling or fan on. The controls activate the relay a timed delay after getting a signal the gas is on. You could have a problem with the controls, most likely the relay, or the flame sensor, or the fan motor. Finding a point to check each component can be tough. Does your furnace give trouble codes by flashing a light?
    seedxpress's Avatar
    seedxpress Posts: 2, Reputation: 2
    New Member
     
    #3

    Oct 20, 2006, 05:42 AM
    I found out I had the wrong settings on my thermostat. I have to change setting HG (gas) to HE (electric) because the electric furnace will not turn on the fan automatically. The thermostat has to force it ON.
    METT's Avatar
    METT Posts: 14, Reputation: 1
    New Member
     
    #4

    Oct 29, 2006, 09:32 PM
    HE setting is needed for electric furnace. HG is for gas furnace which will turn on the fan by itself.
    sucosam's Avatar
    sucosam Posts: 59, Reputation: 1
    Junior Member
     
    #5

    Nov 6, 2006, 12:54 PM
    Changing this same setting also worked for me. The fan would not run unless I changed from Auto to On. But after making this change, mine also now works.
    ayemagnet's Avatar
    ayemagnet Posts: 1, Reputation: 1
    New Member
     
    #6

    Dec 6, 2008, 03:28 PM

    The blower on my furnace will not kick on at times .
    MarkwithaK's Avatar
    MarkwithaK Posts: 955, Reputation: 107
    Senior Member
     
    #7

    Dec 6, 2008, 03:47 PM
    Quote Originally Posted by ayemagnet View Post
    The blower on my furnace will not kick on at times .
    Please post this in a separate thread and provide make, model # and serial #.
    badlefthand's Avatar
    badlefthand Posts: 2, Reputation: 1
    New Member
     
    #8

    Jan 11, 2010, 11:08 AM
    Quote Originally Posted by seedxpress View Post
    I found out I had the wrong settings on my thermostat. I have to change setting HG (gas) to HE (electric) because the electric furnace will not turn on the fan automatically. The thermostat has to force it ON.
    Joined to say,after 2 years and 3 different A/C mech .I followed your advise.Fixed my furnace problem. Thanks,:D
    OpenSesame's Avatar
    OpenSesame Posts: 2, Reputation: 1
    New Member
     
    #9

    Nov 21, 2011, 05:24 PM
    I checked the thermostat fuse and it appears to be good, and the HG Switch is in correct position, and the fan does not engages in either the "auto" or "ON" (manual override) positions. One person thought it might be the "High Limit Switch," however how do I confirm. Like the person above, the fan DOES COME ON for the Air Conditioner, just NOT the HEATER. Any words of wisdom? Thanks in advance.
    starcruiser's Avatar
    starcruiser Posts: 1, Reputation: 1
    New Member
     
    #10

    Jun 16, 2012, 06:06 AM
    New Honeywell TH6110D thermostat does everything it should to run the gas heater.
    But it does not turn on the air conditioner, nor will it run the fan in manual fan mode.

    By removing the thermostat from its base plate, I can run the fan by jumpering G and C (24v common terminal). And can start air conditioner compressor by jumpering the Y terminal.

    I have gone through the settings of the thermostat several times for correct setup.
    Seann's Avatar
    Seann Posts: 32, Reputation: 1
    Junior Member
     
    #11

    Jun 17, 2012, 01:19 PM
    Quote Originally Posted by starcruiser View Post
    New Honeywell TH6110D thermostat does everything it should to run the gas heater.
    But it does not turn on the air conditioner, nor will it run the fan in manual fan mode.

    By removing the thermostat from its base plate, I can run the fan by jumpering G and C (24v common terminal). And can start air conditioner compressor by jumpering the Y terminal.

    I have gone through the settings of the thermostat several times for correct setup.
    Hi
    Remove the C wire
    Connect a jumper between Rc and R and Tape off the C as C is comman and is only used for the power to display

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Furnace Blower Fan Won't Turn Off [ 3 Answers ]

Last night I installed a brand new programmable Honeywell to replace my the ancient mercury Honeywell that was on the wall. I have a 20+ year old forced air gas with central air. The side effect has been that the furnace blower will not shut off. Whether the system is in "heat" or "cool" or...

How to Wire a Thermostat to blower fan for alternate heat source [ 5 Answers ]

Hello all I just built a plenum around my coal stove and I need to wire in a stat , limit switch to run a blower fan . Thanks Steve PS I have all the parts off and hot air oil furnace.

Fan Blower will not come on in auto [ 8 Answers ]

Blower will only come on when in "ON" position. "Auto" position will not cause it to go on. One can hear the thermostat click (basically saying its time to kick in) but the blower will not commence until I manually set it to "ON". At first, I thought it was thermostat so I replaced it with a...