thermostat problems or furnace problems

Is it possible that a thermostat operates correct all the time except when it reaches the temperature that is set doesn't maintain that temperature?
I noticed that actually that thermostat gives a signal to the furnace but furnace doesn't turn on but that happens only when thermostat needs to maintain temperature that is set.
Is it possible that thermostat isn't working at that regime (to hold the set temperature)?

Reply With Quote
 
     

Answers
 
 
Old Nov 19, 2006, 01:25 PM   #2  
Über Member
labman is offline
 
Join Date: Feb 2003
Location: Northern US
Posts: 10,646
labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.
The thermostat is simply an on/off switch. Below a certain temperature it is on. That will turn the furnace on, and heat up the house. Once it gets above the set temperature, the switch opens and shuts the furnace off. It has a little bit of a dead area so that it isn't constantly turning on and off. That can be adjusted. The older ones that relied on a bimetal spring and mercury tilt switch wouldn't work right if not level. Round ones are difficult to get level. Newer electronic thermostats can have other problems.
  Reply With Quote
 
     
 
 
Old Nov 19, 2006, 07:04 PM   #3  
New Member
gautamanne is offline
 
Join Date: Apr 2006
Posts: 9
gautamanne See this member's comment history on his/her Profile page.
I think its your thermostat..See if you can go to your local Home Depot and get a Rite Temp thermostat and call the RiteTemp hotline and have them help you install. Ask for this dude called david. I had a similar problem and was able to isolate by calling these folks ..Otherwise would have costed me a lot to call the tech.
  Reply With Quote
 
     
 
 
Old Nov 19, 2006, 11:37 PM   #4  
Ultra Member
NorthernHeat is offline
 
Join Date: Oct 2006
Location: IN
Posts: 1,380
NorthernHeat See this member's comment history on his/her Profile page.NorthernHeat See this member's comment history on his/her Profile page.
Is this a digital stat? Could there be a heating temperature differential you can change in the user set-up? Is the W wire hooked up to W2 ?
  Reply With Quote
 
     
 
 
Old Nov 20, 2006, 11:10 PM   #5  
New Member
senada is offline
 
Join Date: Nov 2006
Posts: 4
senada See this member's comment history on his/her Profile page.
Yes it's digital, but there is no w2 position only w. Anyway I changed thermostat today and will see how it works.
  Reply With Quote
 
     
 
 
Old Nov 21, 2006, 09:53 PM   #6  
New Member
senada is offline
 
Join Date: Nov 2006
Posts: 4
senada See this member's comment history on his/her Profile page.
Now I know it's not thermostat. Furnace still acts same. Any suggestions what could be a problem. Furnace is 7 years old & it's Lennox G20.
  Reply With Quote
 
     
 
 
Old Nov 21, 2006, 10:28 PM   #7  
Über Member
labman is offline
 
Join Date: Feb 2003
Location: Northern US
Posts: 10,646
labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.
I still don't quite understand the problem. If the furnace and thermostat are working properly, the heat will cycle up and down. When the furnace is on, it heats faster than the house loses heat. When it gets up to a point, the thermostat turns it off. Then the house loses heat until cool enough for the thermostat to turn the furnace back on. If the range is too great, Northern Heat and I both mentioned adjusting it.
  Reply With Quote
 
     
 
 
Old Nov 21, 2006, 11:49 PM   #8  
New Member
senada is offline
 
Join Date: Nov 2006
Posts: 4
senada See this member's comment history on his/her Profile page.
What's happening is that furnace fail to start every time when it reaches set temperature.
It works like this: thermostat gives a signal to start furnace, damper door opens, LED lights turns on, pilot flame shows up, LED light turns off, dumper door remains open, furnace not working. Furnace will never start working even when temperature drops for couple degrees unless I turn off/on furnace on power switch.
  Reply With Quote
 
     
 
 
Old Nov 21, 2006, 11:54 PM   #9  
Ultra Member
NorthernHeat is offline
 
Join Date: Oct 2006
Location: IN
Posts: 1,380
NorthernHeat See this member's comment history on his/her Profile page.NorthernHeat See this member's comment history on his/her Profile page.
OK lets start over. What brand, type, age and efficiency furnace/boiler/heatpump do you have?
  Reply With Quote
 
     
 
 
Old Dec 3, 2006, 04:22 PM   #10  
New Member
simshawk is offline
 
Join Date: Dec 2006
Posts: 3
simshawk See this member's comment history on his/her Profile page.
Quote:
Originally Posted by senada
Is it possible that a thermostat operates correct all the time except when it reaches the temperature that is set doesn't maintain that temperature?
I noticed that actually that thermostat gives a signal to the furnace but furnace doesn't turn on but that happens only when thermostat needs to maintain temperature that is set.
Is it possible that thermostat isn't working at that regime (to hold the set temperature)?
I just posted a similar problem today with the LED displays (User ID: simshawk). My unit is a Lennox Elite Surelight, 6 years old, Nat Gas, using a ritetemp thermostat.

When the desired preset is met, the unit kicks off and will not restart until I perform a manual reset.

Here is my post:

Having the following problem.

Woke this morning and temp in house was 62degs. Check thermostat and it said heating, temp set on 68.

Checked the unit and the diagnostic LEDs were flashing alternatively and slow. According to the Diag Sheet, this is "Watchguard - Burners failed to Ignite".

Shut unit down and waited 15mins, performed a restart and unit was working properly, both LEDs flashing simultaneously and slow.

Temp got to preset value 71 degress and the unit shut down again. Noticed temp went back to about 67 degrees, thermostat was showing heating, but nothing was coming from the vents, and no flame on the unit.

Check LEDs again and saw the same "Watchguard" failure as above. Shutdown unit and performed a restart, heater kicked on, but now the LEDs are #1 slow flash, and #2 fast flash, which according to the status table is "Low flame signal, check flame sensor".

Help, its going to be really cold tonite in MI.

Jerry
  Reply With Quote
 
     

Your Answer
Email me when someone replies to my answer
Join Login



Thread Tools Search this Thread
Search this Thread:

Advanced Search
Display Modes
Ask your question or search...



Similar Threads
goodman furnace problems
(5 replies)
Gas Furnace problems
(3 replies)
Furnace problems
(5 replies)
Problems installing a programmable thermostat
(2 replies)
HELP house furnace thermostat?
(1 replies)

Thread Tools
Show Printable Version Show Printable Version
Email this Page Email this Page
Search this Thread

Advanced Search

Bookmarks





Copyright ©2003 - 2009, Ask Me Help Desk.
All times are GMT -8. The time now is 03:58 PM.