    Signs bad expansion valve home air conditioner
    We have a 2.5 ton heat pump with backup furnace. We have had 3 tech out here to try to get this system working. All said ghost leak freon in. Last guy said no leak could find nothing wrong with system. My husband and I took it upon ourselves to take soapy water and check for leaks and totally cleaned the system a coil, filters(which we change monthly). The system worked for 4 hours with 50 degrees showing out of registers. Then just stopped. Froze up. My husband had checked at 2 hr. point was not froze up. This last guy said it's the expansion valve. We are already over 500.00 in on this unit this spring. Does anyone have any ideas for us or agree with the last tech?? Please help us out Momma is hot! I can't afford much more.
    Thanks in advance!!
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Jun 11, 2012, 07:02 PM
    Quote Originally Posted by jessusa71 View Post
    We have a 2.5 ton heat pump with backup furnace. We have had 3 tech out here to try to get this system working. All said ghost leak freon in. Last guy said no leak could find nothing wrong with system. My husband and I took it upon ourselves to take soapy water and check for leaks and totally cleaned the system a coil, filters(which we change monthly). The system worked for 4 hours with 50 degrees showing out of registers. Then just stopped. Froze up. My husband had checked at 2 hr. point was not froze up. This last guy said its the expansion valve. We are already over 500.00 in on this unit this spring. Does anyone have any ideas for us or agree with the last tech??? Please help us out Momma is hot!! I can't afford much more.
    Thanks in advance!!!!
    Is the inside blower running when the unit freezes up? If the fan is running but it freezes up then it could be the expansion valve. Usually expansion valves last a long time and need almost no service but anything is possible. Sorry to hear about your problems and also the fact that you have had 3 supposed techs looking at it and it is still not fixed. There is a giant shortage of trained people in the HVAC biz. NOTE: Make sure the sensing bulb is tight on the copper line of the coil. Loose thermostatic expansion sensor bulbs can and will cause problems.
    jessusa71's Avatar
    jessusa71 Posts: 2, Reputation: 1
    New Member
     
    #3

    Jun 11, 2012, 07:33 PM
    Quote Originally Posted by hvac1000 View Post
    Is the inside blower running when the unit freezes up? If the fan is running but it freezes up then it could be the expansion valve. Usually expansion valves last a long time and need almost no service but anything is possible. Sorry to hear about your problems and also the fact that you have had 3 supposed techs looking at it and it is still not fixed. There is a giant shortage of trained people in the HVAC biz. NOTE: Make sure the sensing bulb is tight on the copper line of the coil. Loose thermostatic expansion sensor bulbs can and will cause problems.
    Thank You first for such a fast reply! The unit will run everything working fine for about 3-4 hours Then The lines and A-coil freeze up and we already know this before we go down and take the panel off because the cold air just starts to go away. The mechanics of the unit are all working... But I quess my question is... Before I shell out money for a valve, do you think it could be overcharged by the techs? Because before we just cleaned it all up and checked everything we could. It did not get cold at all. At least after we did that it worked for 3-4 hours at a time. This unit is 8 yrs old.Lennox elite series if that helps at all?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Jun 12, 2012, 12:21 AM
    Quote Originally Posted by jessusa71 View Post
    Thank You first for such a fast reply! The unit will run everything working fine for about 3-4 hours Then The lines and A-coil freeze up and we already know this before we go down and take the panel off because the cold air just starts to go away. The mechanics of the unit are all working...But I quess my question is...Before I shell out money for a valve, do you think it could be overcharged by the techs? Because before we just cleaned it all up and checked everything we could. It did not get cold at all. Atleast after we did that it worked for 3-4 hours at a time. This unit is 8 yrs old.Lennox elite series if that helps at all??
    Naturally from here it is hard to tell exactly what the problem is since without being able to see the unit and do testing most of what we tell people is some guess work.

    Usually a freeze up is caused by dirty filters,obstruction in duct work,closed registers or blocked return air. Other causes can be shortage of refrigerant, indoor blower motor overheat and turning off during operation etc. Sorry I cannot be more exact but I cannot see it and test it from here.

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

Air conditioner/furnace combo in mobile home is blowing cold air [ 8 Answers ]

This is an all electric mobile home that has an outside air conditioner with heating system. It is blowing cold air when the heat is turned on at the thermoniter.

Air conditioner blower motor how to know when bad? [ 0 Answers ]

The air conditiner seems to short cycle even though the house is plenty hot. The air comes out nice and cool as low as 58f to 59f. When I was checking the unit the coil's seem to over cool when the fan shut off and the compreesor was still going. I turned the unit to fan only it would run for a...

My central home air conditioner is blowing cold air but making a loud noise [ 2 Answers ]

My central home air conditioner is blowing cold air and seems to be running fine however all of a sudden it began making a loud noise inside like a Hummm, HUmmm, HUmmm noise when running. Should I expect this thing to die?

Amana air conditioner rhe60c2a 5.0 ton king valve [ 1 Answers ]

What's best approach... remove... solder line... more expensive... or replace. Thanks


View more questions Search