    handynot's Avatar
    handynot Posts: 8, Reputation: 1
    New Member
     
    #1

    Sep 24, 2008, 08:05 AM
    Run a Lennox Furnace on Generator power
    Hello All,
    Can I run my newer (2004) NG Lennox Furnace on the Generator?

    Sorry I don't have the model # but I am sure it is a "Builders Special"

    Or should I just use that circuit for General Lights on my Transfer Switch?


    Thank You in Advance!!
    ballengerb1's Avatar
    ballengerb1 Posts: 27,378, Reputation: 2280
    Home Repair & Remodeling Expert
     
    #2

    Sep 24, 2008, 08:50 AM

    Could you give me more details about what you said here "Or should I just use that circuit for General Lights on my Transfer Switch?

    " Depending on the size of the generator, and your panel, you can power more than one circuit with the generator.
    handynot's Avatar
    handynot Posts: 8, Reputation: 1
    New Member
     
    #3

    Sep 24, 2008, 09:35 AM
    Quote Originally Posted by ballengerb1 View Post
    Could you give me more details about what you said here "Or should I just use that circuit for General Lights on my Transfer Switch?

    " Depending on the size of the generator, and your panel, you can power more than one circuit with the generator.
    "Details:

    Coleman Powermate 5kw Maxa ER Plus (pm0525312.17)

    using the L14-20 receptical with Floating Neutral

    10/3 W/ground Bus Drop cable (35 ft) to EmerGen transfer switch (Conn elec. #60-5000)

    Cuttler Hammer Main"

    I have the 5 other circuits wired (sump, Ref, general lights ect)

    I also wanted to run my furnace on the Generator
    (that was my MAIN reason for going through the main panel)
    But in reading other posts it seems that

    They are real fussy with them (so are Arc Fault breakers).

    I just wanted to see if anyone had any positive connections for emergency power outages.

    OR

    Should I just give up trying to run the furnace and use that last circuit for something else?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Sep 24, 2008, 10:11 AM
    Float ground NO GOOD. Check for other design/ground applications (more than one is available)
    The newer style furnaces depend upon a good solid ground for the electronics!
    The generator should work just fine but you will need to take current draws of different circuits to see which ones will run together without overloading the gen set or create feedback on the neutral/or ground..
    Been there done that.

    Note you can daisy the breakers to allow run time on each device or devices but the load will have to be changed manually. (see current (amp) draw comments above.
    handynot's Avatar
    handynot Posts: 8, Reputation: 1
    New Member
     
    #5

    Sep 24, 2008, 12:24 PM
    [QUOTE=hvac1000;1290308]Float ground NO GOOD. Check for other design/ground applications (more than one is available)The newer style furnaces depend upon a good solid ground for the electronics!

    I thought that the ground was attached thru the bus cable and into the Main panel ground (Neutral & Ground are attached inside).
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #6

    Sep 24, 2008, 12:54 PM
    That is fine for your main service BUT not for a separately derived system service. There are way to many NEC codes that come up when gen sets come into the disscussion.

    Please check with a qualified electrician in your area as to the proper wiring as per the NEC and have your work inspected by a state or local inspection agency if required in your area. There is a guy down the line working on the utilitys side of the system that will appreciate not getting killed by someone's mistake. That happened not so long ago in my area.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #7

    Sep 24, 2008, 01:07 PM
    Cheater's delight LOL

    http://www.dslreports.com/speak/slid...EtZ2VuZXJhdG9y

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search


Check out some similar questions!

Use inverter to increase power output of a generator [ 7 Answers ]

Hello does anyone know if it is practical or even possible to amplify the power of a small generator using a large watt inverter? Say you have a 2 or 3 HP 1000 watt generator and you hook it up to a 5000 watt inverter. What kind of power will you be NOW able to generate? Doesn't the horse power of...

Generator power transfer switch [ 1 Answers ]

Our power goes off on a frequent basis. If it is off more than 8 hr I need to power up with my own generator 8kw, to prevent spoilage and to run the well. My question is do you have to disconnect the neutral also and run the neutral to the generator or can the neutral be common to both power...

What to look for when purchasing a power generator [ 7 Answers ]

I'm building a emergency home kit and will be purchasing a portable generator for this kit. I'm looking at a 2.4 hp 1000 watt max/960 rated generator, I'm not sure if a 120v, 8 amp ac receptacle can run anything larger than a handtool. Is there some kind of listing of what can be operated and how...

Generator power output cuts in and out [ 1 Answers ]

Bought a Coleman Generator a few months ago and I have it connected to an inverter. The inverter is connected also to 16 "deep cycle" batteries and usually powers the house from solar panels. Everything has been working terrific until last night when the generator began cutting in and out. It...

Battery backup power for Lennox G61MPV furnace? [ 4 Answers ]

I would like to be able to operate my 2004 Lennox G61MPV furnace using a 1200W, 12V DC to 110V AC power inverter. The blower works just fine, but as soon as it tries to ignite, the furnace shuts down. I suspect it may be a question of proper grounding--the furnace may be very sensitive to this. ...


View more questions Search