    RTH7500D honeywell help please
    I bought a Honeywell RTH7500D and am trying to install it, but (as appears to happen frequently) the wiring guide in the install manual does not match the wire labels from the old, non-programmable Stat.

    What I have in the OLD one:

    V
    RH
    RC
    G
    Y

    I believe the proper wiring is:

    G=G
    RC=RC
    Y=Y

    but

    what do I do with the RH and the V wire? I appreciate any help. My HVAC is a conventional system.

    Also, note that the RC is jumpered to the RH in the old stat.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    May 15, 2006, 01:50 PM
    Is this a Heat Pump system? Never heard of V terminal. May be a reversing valve on a Heat Pump.

    If this is only a standard heating cooling system, is it possible the V is actually a w?

    Rc and Rh allow for separate control sources, one for heat and one for cooling. Many times there is only one source, therfore Rh and Rc get jumped.
    ipsolutions's Avatar
    ipsolutions Posts: 2, Reputation: 1
    New Member
     
    #3

    May 16, 2006, 08:31 PM
    OKay, after more unplugging and replugging, it is not a V terminal but a W terminal, and I know where that goes.

    But I discovered I have 2 wires from wall going to the Y terminal. One is an open wire end, the other is an o-shaped end, both plugged into the old White-Rodgers Y terminal.

    Any idea what to do with the extra (o-shaped) Y wire?

    FYI link to my current W-R instruction manual is found here: http://www.white-rodgers.com/wrdhom/.../0037-5026.pdf.

    It appears the extra Y is a factory installed jumper. Do I just leave that unconnected in the new honeywell?

    Thanks.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Honeywell thermostat [ 11 Answers ]

I installed a Honeywell CT87A 4447 thermostat this summer. It worked fine with my air conditioning, but I am having a problem with it controlling my furnace. It will turn the furnace on and I can turn the fan on manually, but when set to auto the fan does not come on. The thermostat has the...

Honeywell RTH230B [ 3 Answers ]

I currently have a very old thermostat, White-Rodgers 135-415, which I'd like to convert to a Honeywell RTH230B. Currently there are only 3 wires that are connected to the thermostat (which is only for my apartment's heat. White wire is connected to what looks to be labeled "Common" Black...

Help with new Honeywell RTH7500D [ 1 Answers ]

Hello Everyone. I just bought my new thermostat and installed it. Using my old thermostat, an old mercury White-Rodgers, I wiring the Honeywell to what I thought was a "conventional" system. I have gas heat and electric A/C. Outside I have the fan unit which blows air into the compressor and...

Honeywell RTH230B [ 6 Answers ]

I am installing a Honeywell RTH230B thermostat but am not sure of the wiring. I have 6 wires colored as follows, red, green, white, yellow, and 2 blue wires. Please advise?

Honeywell Pro Th411od [ 1 Answers ]

Should My Thermostats Panel Operate On The 2 Aa Backup Batteries Or Be Hardwired To Common And Have Batteries As Backup When Power Is Out? Panel Lights Up With Batteries In, Does Not Without Batteries. Don't Know Where Common Wire Originates From. Can I Splice Into One Of The Other Wires, G, Y,...


View more questions Search