    Rheem Criterion II blower works but no flame
    My furnace blower starts runs for a few minutes and then stops. The two green LEDs are on-the amber one is not. The igniter does not get hot. Dead igniter?
    Thanks
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #2

    Dec 14, 2009, 03:58 PM
    By furnace blower, which one you talking about ? The smaller inducer motor or the much bigger blower that blows air into your living space,
    It makes a difference as to what kind of an answer to give you
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #3

    Dec 14, 2009, 04:20 PM

    If at no time the glow plug glows, check for 120v at glow plug connection when it should be glowing. If it is getting 120v, then yes, your igniter is bad. If you don't ever get voltage to glow plug, then I would start looking at pressure switches, and please answer wmproops question as to whether or not the draft inducer blower is coming on when there is a call for heat.
    PahaPlager's Avatar
    PahaPlager Posts: 4, Reputation: 1
    New Member
     
    #4

    Dec 15, 2009, 07:57 PM

    Actually, yes, both blowers function. There is no juice to the igniter and the amber LED does not light-only the two green LEDs. I just replaced the motherboard with a new and the same result-blowers and no juice to the igniter. Heat sensor dead?
    PahaPlager's Avatar
    PahaPlager Posts: 4, Reputation: 1
    New Member
     
    #5

    Dec 15, 2009, 08:24 PM

    Sorry gentlemen, I was wrong. Only the smaller inducer fan runs, the big fan does not run. My mistake.
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #6

    Dec 16, 2009, 03:45 PM
    OK, the bigger blower won`t run till the heat exchanger get to a certain degree, chances are you are in need of a igniter,, but to be sure you should do as mygirlsdad said,, check for 120 volts to the igniter before you replace igniter,you could possible remove the igniter (very carefully) because they break very easy and inspect for cracks,burned spots that are pretty easy to see
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #7

    Dec 16, 2009, 04:51 PM
    Quote Originally Posted by PahaPlager View Post
    . There is no juice to the igniter and the amber LED does not light-only the two green LEDs.
    Okay, if no voltage to igniter, I'm guessing you have a pressure switch problem(cuased by plugged exhaust or combustion air vents, plugged pressure switch hoses or ports, plugged drains hoses or trap, weak draft inducer, or bad pressure switch). The amber light will only come on when flame is sensed(burners are fired), so its normal for the amber light to be off if there is no flame. First, check to make sure your intake and exhuast vents are not froze up(or obstructed in any way) on the outside of the house. Next, clean drain hoses, ports and trap, also clean the port where the pressure switch hose hooks to the draft inducer, and also the one where the other pressure switch hose hooks to the heat exchanger. Do these things and let us know what you find.
    PahaPlager's Avatar
    PahaPlager Posts: 4, Reputation: 1
    New Member
     
    #8

    Dec 16, 2009, 11:22 PM

    Gentlemen-I can't thank you enough. Your skill and expertise has guided me to the problem and, more importantly, its solution. I have a warm house once again thanks to you. Indeed, the pressure switch was the problem. It's limping along now but tomorrow I know what to buy and replace. Thank you so much!
    Doug

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Rheem Criterion II - blower works OK with heat or AC, not by itself [ 1 Answers ]

The problem appears to be in the internal wiring or control board. Symptom: If I temporarily connect the red low voltage control wire from the transformer to the green control wire for the fan, a relay clicks on the control board. But the blower does not come on. I have tried re-seating...

Rheem Criterion II Flame Cutting Off & On [ 2 Answers ]

I have a Rheem Criterion II furnace that recently will sometimes work fine and other times the flame will kick on and heat up, then when the blower kicks on after about 5 seconds the flame goes off and the blower keeps going. The flame kicks on about 3-4 times every minute or so and after the 4th...

Rheem Criterion II--heat cycle works, then shuts down [ 2 Answers ]

Hi- I'm having a problem with my gas furnace and don't know where to start to find out what it might be. When the thermostat calls for heat, the draft inducer kicks on, the ignitor glows, the gas starts and burns for a short time and then shuts off. It tries this whole cycle again, with the same...

Rheem Criterion II blower won't stop [ 4 Answers ]

I have a Rheem furnace and the low speed fan continues to stay on after the furnace has cycled off. When I disconnect the red wire (low speed wire), the furnace runs normally. I would imagine the switch for the low speed is open. Is the switch controlled by the IFC? Does the IFC need to be...

Blower turns on and off / flame works fine [ 1 Answers ]

I have a Luxaire Delux High Efficiency Furnace (PBNU-LD12N1000)that probably isn't to efficient since it's about 15 years old. I recently bought a new home and have had trouble with the blower in the furnace turning off before the house is heated to the correct temp. It will then turn itself back...


View more questions Search