    Rheem 10seer heat pump
    Unit cooling fan comes on power to compressor 246.6 volts but the compressor is not working. Is my compressor toast or what. The compressor is hot to touch and the lines are not cool. Been having trouble with the relay contacts arching and losing contact but not now just not cooling.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Jul 27, 2012, 09:54 PM
    Quote Originally Posted by Josh Duco View Post
    Unit cooling fan comes on power to compressor 246.6 volts but the compressor is not working. Is my compressor toast or what. The compressor is hot to touch and the lines are not cool. Been having trouble with the relay contacts arching and loosing contact but not now just not cooling.
    Let the compressor completely cool. Then take your meter and give the compressor a OHM test and also a test to ground. This will tell you an aprox condition of the compressor. If that all checks well and it is a single phase compressor (Usually residential) then you can also test the run capacitor as well as the start capacitor if used. You should also test the start relay for the start capacitor as well as the main contactor for the conditions of the contacts.
    Attached Images
      
    TopTechnician's Avatar
    TopTechnician Posts: 9, Reputation: 1
    New Member
     
    #3

    Jul 28, 2012, 08:14 PM
    That contactor is a $15 part that may have cost you a compressor. Contactors should be replaced at the first sign of trouble, if not before! Replace yours at least every 5 years; sooner if it looks burnt.
    Of course, if you are using a service company, it might cost you $200 to have that $15 part replaced.

    Before giving up on the compressor, try a start-assist capacitor. If you already have one, try a new one. A common type is called an SPP6; they are cheap and EASY to install. This will help the compressor get started. When a compressor won't start, it gets hot and an internal overload opens up, disconnecting power.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

I have a new Rheem heat pump. The cooling works fine but won't blow hot air in HEAT [ 1 Answers ]

I have a new Rheem heat pump. The cooling works fine but won't blow hot air in HEAT setting. I have reset the breakers for heat pump and air handler, changed filters and pulled batteries and reset the Braeburn 3000 thermostat. Still blows cold... Any other suggestions?

Rheem heat pump [ 0 Answers ]

I have a Rheem Heat Pump. I had the a/c technician come out the other day for the second time to fix the unit from blowing warm air consistently. He fixed that but a new problem has risen. I have the heater set at 67 degrees. Once the temperature in the house drops below 67 degrees, the unit...


View more questions Search