    loddy's Avatar
    loddy Posts: 3, Reputation: 1
    New Member
     
    #1

    May 4, 2008, 09:44 AM
    R410 mini split has cold liquid line
    I have a R410 mini split. Flare fitting leaked so I pulled all the gas out and fixed the leak ,
    Put it in a vacuum and weighed in the charge. Unit came on and cooled but liquid line was very cold. Suction pressure was about 120 and 37 degrees. Well I went away for awhile and came back later. Both fans were running
    But compresser was not. Unit is 1 yr old. My question is should the lquid line be that cold and did I damage the compresser? This unit does not have a high side port.
    aldematt57's Avatar
    aldematt57 Posts: 18, Reputation: 2
    New Member
     
    #2

    May 4, 2008, 09:51 AM
    Even without a service access port on the high side, you could have checked it's temperature and thus determined the pressure on the high side using a PT chart.
    What you are describing is a compressor valve failure and a compressor shutting down on thermal overload.
    loddy's Avatar
    loddy Posts: 3, Reputation: 1
    New Member
     
    #3

    May 5, 2008, 07:21 PM
    Suction line was very cold so really didn't need to take temp. if valves were bad why did I have good suction line presssure when compresser was running.
    aldematt57's Avatar
    aldematt57 Posts: 18, Reputation: 2
    New Member
     
    #4

    May 6, 2008, 08:01 PM
    Sorry. For some reason I thought you were dealing with R-22. My bad.

    Can you jumper out some safety switches and see if the compressor continues to run?
    It's possible that a low or high pressure control could be taking the compressor out.
    What are your amp draws when the compressor is running?
    hvacservicetech_07's Avatar
    hvacservicetech_07 Posts: 1,083, Reputation: 75
    Ultra Member
     
    #5

    May 6, 2008, 09:15 PM
    Well, Is your TXV inside the outdoor unit? If so, that would make your liquid line cold. I know a lot of the ductless split systems do that. Have you put gauges back on the system since it has went out? Is it possible that you may have lost refrigerant?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #6

    May 6, 2008, 09:58 PM
    ((put it in a vacuum and weighed in the charge))

    Did you just let the unit compressor put it in a vacuum or did you use a vacuum pump and pull it down to the proper microns? If you just used the units compressor instead of a real good vacuum pump you probably have noncondensibles in the system causing a floating restriction which would allow the frost on the line to come and go as the restriction moved around in the system.
    gottee's Avatar
    gottee Posts: 7, Reputation: 1
    New Member
     
    #7

    May 11, 2008, 09:06 PM
    Ductless with only a single access port have the expansion valve on the inside of the outdoor unit. This is why both lines are insulated and it is not a liquid line, technically it would be referred to as the condensate line. Normally the Manu tells you what temp difference to look for between both lines. Inside the condensing unit is where you can find the high side access port if you need it.

    P.S. With R-410 units, do yourself a favor and DON'T jumper the high pressure switch
    mrblondie's Avatar
    mrblondie Posts: 2, Reputation: 1
    New Member
     
    #8

    Jun 29, 2010, 11:10 AM
    Help got my r410 split installed and the guy didn't vacuum line, only access on the big pipe I'm guessing its low side.valves were opened the ac works and so does heat but I know its not right please help what do I do service companies don't want to come for less than 800 do can u but a pump and recover the gas then vacuum line please help I saw a pump on eBay 9k268 or something like that what is needed
    mrblondie's Avatar
    mrblondie Posts: 2, Reputation: 1
    New Member
     
    #9

    Jun 29, 2010, 11:10 AM
    Help got my r410 split installed and the guy didn't vacuum line, only access on the big pipe I'm guessing its low side.valves were opened the ac works and so does heat but I know its not right please help what do I do service companies don't want to come for less than 800 do can u but a pump and recover the gas then vacuum line please help I saw a pump on eBay 9k268 or something like that what is needed
    sirjusingh's Avatar
    sirjusingh Posts: 1, Reputation: 1
    New Member
     
    #10

    Sep 19, 2011, 05:33 PM
    What gas pressure to use when gas r410 split unit 12000btu
    shaddoe's Avatar
    shaddoe Posts: 1, Reputation: 1
    New Member
     
    #11

    Jul 31, 2013, 11:45 AM
    Quietside minisplit with two air handlers with multiport outside unit ran fine for 2-3 weeks then indicated low pressure this is 410 system charge was correct at installation suspected leak reclaimed Freon pressure checked no leaks what could give low suction reading??

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search


Check out some similar questions!

New AC installation - should both liquid and suction line dryers be installed? [ 7 Answers ]

To make a long story short I've have a bad experience trying to get some repairs done to an existing aire-flow unit. $800 later I'm scrapping the unit. I've ordered (online) a new Rheem Classic 3 ton 13 seer condenser, coil and 100,000 BTU gas furnace. I am not going to try to install the unit...

Mini-Split wiring [ 12 Answers ]

I am installing a Mitsubishi mini-split with an indoor and an outdoor unit (MUZ-A15NA). I ran 220V wire from the electrical box outside. It is on a 15 amp breaker as the instructions have it rated as 15 amp max. I purchased a disconnect switch for the outdoor unit that is a 60 amp fuseable...

How does the phone company split one line into two [ 4 Answers ]

I have either read or been told that the phone company can electronically split single line service to a residence and provide a second phone number resulting in two separate phones being provided through the same wire to the house. How do they do this?

"Popping noise" coming from mini-split AC unit [ 1 Answers ]

We have an "AllStyle" brand mini-split AC in our bedroom. It's about 1.5 years old. It works fine, except about a month ago, it started "popping" and "cracking"--making it virtually impossible to get a good night's sleep! The sound is like that of plastic-on-plastic expanding or contracting...

Mini split Problems! Turns off [ 4 Answers ]

Hi, I have a couple of mini split ac's and am having some issues. One works fine for about 10-30 minutes and then just turns off. Fan stops but it puts out cold air when it runs. This one is a bondaire r22 unit. I have another 33,500 BTU dual zone mitsu mr slim 17+17. This unit doesn't cool...


View more questions Search