  • Mar 1, 2009, 12:24 PM
    SCOTTG1984
    Pressure switch stuck open gibson furnace
    I have a gibson forced hot air furnace and a have a code that is telling me that the pressure switch is open. If I drain the water out of it it will run for a short period.. Do you think I need a new pressure switch or do I have a drainage line clogged.
    Model number KG6R060C-12a
  • Mar 1, 2009, 01:15 PM
    KC13
    Where are you draining the water from? If this action restores function for a while, I suspect you have clogged hoses or condensate trap.
  • Mar 1, 2009, 01:26 PM
    SCOTTG1984
    Quote:

    Originally Posted by KC13 View Post
    Where are you draining the water from? If this action restores function for a while, I suspect you have clogged hoses or condensate trap.

    I pulled the hose off the pressure switch and water drained out. Is that normal?
  • Mar 1, 2009, 02:44 PM
    KC13
    Quote:

    Originally Posted by SCOTTG1984 View Post
    I pulled the hose off the pressure switch and water drained out. Is that normal?

    Definitely not. The furnace is accumulating condensate, probably due to a clogged hose or trap. Remove the pressure switch and shake it to see if any water comes out. If so, it is likely damaged.