    Payne furnace won't stay lit
    I have a payne furnace model PG8MAA036070AAJA I already removed the flame sensor and cleaned it. That did not help so I went on and bought another one and that still hasn't helped. So when you first get it going the burners only stay on for about 2-3minuutes and then turn back off. The house is freezing. I have no idea on what else to do. Please help I don't have money to call a PROFESSIONAL.
    T-Top's Avatar
    T-Top Posts: 1,871, Reputation: 100
    Ultra Member
     
    #2

    Feb 4, 2011, 06:36 PM
    You should have a light on the control board blinking when the system faults out. Count the blinking light. CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.
    CONTINUOUS ON - Control has 24VAC power.
    RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.
    LED CODE STATUS
    11 NO PREVIOUS CODE - Stored status code is erased automatically after 72 hours. On
    RED LED boards stored status codes can also be erased when power
    (115 VAC or 24 VAC) to control is interrupted.
    12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90 seconds,
    If unit is powered up during a call for heat (R-W closed) or R-W opens during blower
    On-delay.
    13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit, draft safeguard, flame rollout, or
    Blocked vent switch (if used) is open longer than 3 minutes.
    - Control will auto reset after three hours. - Refer to #33.
    14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
    21 GAS HEATING LOCKOUT - Control will NOT auto reset.
    Check for: - Mis-wired gas valve -Defective control (valve relay)
    22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is deenergized.
    Inducer will run until fault is cleared. Check for: - Leaky gas valve
    - Stuck-open gas valve
    23 PRESSURE SWITCH DID NOT OPEN Check for:
    - Obstructed pressure tubing. - Pressure switch stuck closed.
    24 SECONDARY VOLTAGE FUSE IS OPEN Check for:
    - Short circuit in secondary voltage (24VAC) wiring.
    If status code recall is needed, briefly remove then reconnect one main limit wire to display stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After
    Status code recall is completed component test will occur.
    327596-101 REV. B
    31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than five minutes,
    Inducer shuts off for 15 minutes before retry. Check for: - Excessive wind
    - Proper vent sizing - Defective inducer motor
    - Low inducer voltage (115VAC) - Defective pressure switch
    - Inadequate combustion air supply - Disconnected or obstructed pressure tubing
    - Low inlet gas pressure (if LGPS used) - Restricted vent
    If it opens during blower on-delay period, blower will come on for the selected blower
    Off-delay.
    33 LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent
    Switch (if used) is open. Blower will run for 4 minutes or until open switch remakes
    Whichever is longer. If open longer than 3 minutes, code changes to lockout #13.
    If open less than 3 minutes status code #33 continues to flash until blower shuts off.
    Flame rollout switch and BVSS require manual reset. Check for: - Restricted vent
    - Proper vent sizing - Loose blower wheel. - Excessive wind
    - Dirty filter or restricted duct system.
    - Defective blower motor or capacitor. - Defective switch or connections.
    - Inadequate combustion air supply (Flame Roll-out Switch open).
    34 IGNITION PROVING FAILURE - Control will try three more times before lockout #14
    Occurs. If flame signal lost during blower on-delay period, blower will come on for the
    Selected blower off-delay. Check for: - Flame sensor must not be grounded
    - Oxide buildup on flame sensor (clean with fine steel wool).
    - Proper flame sense microamps (.5 microamps D.C. min. 4.0 - 6.0 nominal).
    - Gas valve defective or gas valve turned off - Manual valve shut-off
    - Defective Hot Surface Ignitor - Control ground continuity
    - Low inlet gas pressure - Inadequate flame carryover or rough ignition
    - Green/Yellow wire MUST be connected to furnace sheet metal
    45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;
    - Gas valve relay stuck open - Flame sense circuit failure - Software check error
    Reset power to clear lockout. Replace control if status code repeats.
    SERVICE
    COMPONENT TEST
    EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Furnace burners ignite but won't stay lit on my trane xe78 furnace? [ 0 Answers ]

I have a Trane XE78 furnace and the flames come on for about 5-10 seconds and then shut off. They re-ignite about 10 seconds later, then shut off 5-10 seconds after the 2nd ignition. I believe they flame on one more time, shut off and then never re-ignite and the blower just runs and runs with...

York diamond 80 furnace won't stay lit [ 0 Answers ]

York Diamond 80 burners will not stay lit. They go out after 5 - 10 seconds.

Furnace burner won't stay lit [ 2 Answers ]

I have an older model Night & Day model c100u series 510 gas furnace. The burner won't stay lit when the thermostat kicks on. I replaced the thermocouple but the burner still lights then immediately goes out. Any help?

Goodman furnace won't stay lit [ 1 Answers ]

I have a goodman furnace that goes like this. Inducer fan comes on, 10 secs later glow lights up, 10 secs later get blue flames 10 secs later blue flames goes out. Repeats 3 times I have replaced the flame sensor still same problem But here is the thing. I am only getting 10 volts to the...


View more questions Search