    Outside unit running but no air blowing from vents
    Hi all, here is my question. I came home from work and the house was cool but I thought I smelled a slight burning scent. After a while I stopped smelling it so I forgot about it. About 2 hours later I noticed it was getting warmer in the house so I looke at the thermostat and the temp had gon from 70 to 78. The unit outside was working but no air was coming out of the vents. I checked all breakers and they are fine.
    After an hour I turned on the thermostat and it worked for about 30 minutes and then it stopped blowing through the vents again.
    My air handler is in the crawl space and I have not gone down there yet to check it out. I don't know anything about air handlers... is there a fan in there that could go bad? Since the outside unit is running it must be a problem with the air handler, right?
    Thanks!
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Jun 10, 2009, 09:05 PM
    From the sound of it either your blower motor on the inside unit is defective or it is a remote possibility the capacitor for that motor has failed. Many times when the capacitor has failed it can cause the motor to run hot (that is probably what you smelled). The capacitor and motor need to be checked out using the proper meters. If the motor needs replacement always replace the motor capacitor with a new one sized for the new motor.

    One more item. It could also be that your evaporator coil is freezing up from your system being low on refrigerant. I thought I would mention this fact just in case the motor checks good.

    NOTE: I would shut the power off to the outside unit until the indoor section is repaired.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #3

    Jun 11, 2009, 03:38 PM
    Quote Originally Posted by hvac1000 View Post
    I would shut the power off to the outside unit until the indoor section is repaired.
    That is really kind of you to offer. I'll ride shotgun and hold the light for you if you like. :p
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Jun 11, 2009, 05:22 PM
    At my age someone would probably have to hold the light an carry the tool bag. LOL
    Peter Hammoura's Avatar
    Peter Hammoura Posts: 2, Reputation: 1
    New Member
     
    #5

    Jun 24, 2009, 08:34 PM

    It turned out to be the motor in the air handler. It's working fine now. Thanks!
    But on a different note... I notice a lot of water condensating on the bottom of my air handler... a lot of water. The water from the drip pan is draining fine to the outside of the foundation through a 15 foot pvc pipe. Is all this water on the outside of the handler common because it's in the crawl space instead of the attic?
    Thanks!
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #6

    Jun 25, 2009, 02:26 AM
    If you do not have the floor of the crawl space covered with 6 mil vapor barrier it is. Crawls are always damp and the cold metal acts like another evaporator drawing the moisture to it.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Central AC blowing warm air, outside unit not running [ 3 Answers ]

My question is the following: My inside central AC is blowing warm air. I've checked the thermostat, its OK, I've checked the breaker and that seems OK. This started after a power outage that we had about 2 weeks ago and my unit outside does not run when the inside unit is running. In fact,...

AC unit running but no air blowing from registers. [ 1 Answers ]

We have a Carrier 38TRA048 4 ton AC unit. This replaced our original "builders" model and has always worked great and is very quiet. Today, 104 degrees outside, the AC stopped blowing air out of the registers. The big fan in the Carrier unit outside is blowing and seems to be sucking out the...

Air/heating unit outside running but not blowing air into home [ 1 Answers ]

Was wondering if anyone would know, my main unit outside, will turn on,fans on it are running, but its not cooling house, no air coming threw vents in house, if we leave air/heating unit running outside ,it starts to sweat,theirs water on top of the unit, not sure if its freezing up or not ,it was...

Hot air not blowing out of vents [ 1 Answers ]

Furnace kicks on, but air blows cool (not quite warm). Thermostat is in bedroom #2 and only has the job to heat itself plus bedrooms 3 & 4, but bedrooms 3 & 4 are like freezers. Filters are cleaned regularly.

AC Unit Running but No air through Vents [ 18 Answers ]

I have a 2 story home and the AC unit for the bottom floor is not working properly. Unit is running outside, but no air period is coming out of the vents. I went into the crawlspace and nothing is blocking the duct work. I opened the panel on the side of the AC unit and the coil has frost on it....


View more questions Search