| If the gas comes on and quickly goes off, the sensor, Limit or Flame rollout switch, that tells the controls the gas lit is not working. It will be around the heat exchanger and have 2 wires running to the controls. Make sure it is clean and properly connected. If the furnace still won't work, replace it.
If the gas never comes on at all, check the gas valve for 24 volts across its terminals. If not, make sure usually a blue wire connects to one side of the transformer, and usually a white wire connects to the W terminal of the controls. The white wire in turn should be connected to the red wire at the thermostat. |