    Nordyne Model # E2EB-023HB
    Maybe you guys can help me. My heater will come on for about a minute or so, then kick off for about 30seconds and repeats this cycle. I have replaced the 2 contacts as I was told that might be the problem. Still does the same thing. I have cleaned the a-coils,. etc... as well...


    Any suggestions... Gonna get cold soon LOL

    Mike
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Oct 22, 2008, 06:19 AM
    http://www.nordyne.com/Literature/710193.pdf


    http://www.nordyne.com/Literature/7103200.pdf

    You need to find out which control is dropping out of the circuit allowing the unit to turn off.

    A quick test suggestion. Turn on the fan so it runs all the time then turn up the thermostat to make the heater section turn on after fan is running. By doing this I am trying to eliminate the limit switches from overheating if a fan switch is the problemand also making sure the fan motor is operational.

    Wiring diagrams are above.

    If you have the optional blower relay package this diagram will work.

    http://www.nordyne.com/Literature/707545a.pdf
    mr500's Avatar
    mr500 Posts: 181, Reputation: 8
    Junior Member
     
    #3

    Oct 22, 2008, 06:35 AM
    Quote Originally Posted by hvac1000 View Post
    http://www.nordyne.com/Literature/710193.pdf


    http://www.nordyne.com/Literature/7103200.pdf

    You need to find out which control is dropping out of the circuit allowing the unit to turn off.

    A quick test suggestion. Turn on the fan so it runs all the time then turn up the thermostat to make the heater section turn on after fan is running. By doing this I am trying to eliminate the limit switches from overheating if a fan switch is the problemand also making sure the fan motor is operational.

    Wiring diagrams are above.

    If you have the optional blower relay package this diagram will work.

    http://www.nordyne.com/Literature/707545a.pdf
    I don't have the optional relay on the fan. Just the one round capacitor as far as I know. I will try the fan on, then turn on heat and see what that does. Now, if the heat works what would my next step be? I take it you think that is it overheating and turning off.. Could be it I'm not sure. Also I will check contunity of the small limit switches that are attached to the heating elements... wires unplugged. I was told each wire shold have 24v. Im not getting that at the connecttors. Even with the elements ON, I can't get 24v. Ill try it again tonight when I get home. I might have done it wrong. But its not rocket science to chek 24v with a meter, but then again I don't know lol. Ill re-post when I know more.

    Thanks
    Mike
    mr500's Avatar
    mr500 Posts: 181, Reputation: 8
    Junior Member
     
    #4

    Oct 22, 2008, 05:43 PM
    OK I turned on the fan, then the heat and damn the heat stayed on.

    I noticed too that the fan alone blows a lot harder than when I turn on just the heat/fan.

    So I guess what's my next step. Replace another gadget? More testing?

    Least I know now I can get the heat ON, I just can leave it on all night... thats a plus side..


    Mike
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #5

    Oct 22, 2008, 06:14 PM
    I provided all the wiring diagrams so you can test the components to see which one has failed and does not allow the blower to come on which in turn might be tripping a limit causing the heater to cut off.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Nordyne model E2EB-012HA wiring schematics [ 7 Answers ]

Please help I have a husband that is Hospice patient and need wiring schematic for this ac unit. My brother started working on it and now cannot wire it back together. Heat/air unit and he got the heater working for the cold weather but now he can't figure out what the wires are for air...

Wiring Diagram For Nordyne E2EB-017HA [ 4 Answers ]

I depespeatly need a wiring diagram for this unit. Any help would be great. Thanks

Nordyne e2eb-15hb furnace : [ 2 Answers ]

my furnace thermostat displays all modes & the letters HP when trying to go into emergecy heat( 15kw electric)

Nordyne wiring diagrahm for E2EB heater [ 1 Answers ]

I have a nordyne heating the Ac relay has burned out I need to purchas new relays and find a wiring diagrahm for the heater to rewire

Nordyne E2EB-020 Ha. Ac/Heater, having problems [ 3 Answers ]

I have a Nordyne Model # E2EB-020HA, SER # E2E010105593. Have had problems with this unit. Had a heating contractor come out 3 times, but still have same problem. You turn the ac on, it runs good for a while. When it cuts off, the heating coils come on and stay on, but blower does not come on....


View more questions Search