    Nordyne LED blinkin codes
    Can someone give me the codes for all the Nordyne LED blinks?

    My furnace was blining 4 times, I replaced the igniter and now it is blinking 2 times...

    All the codes would be greatly appreciated - thanks, in advance. :cool:
  • Dec 8, 2007, 05:45 PM
    hvac1000
    2 blinks. Pressure switch is open with inducer fan on.

    4 blinks Ignition failure (check ground)
  • Dec 10, 2007, 06:52 AM
    g_lundy
    Thanks for the info, but...

    ... are those the only 2? What if it blinks once, three or five times?
  • Dec 10, 2007, 08:46 AM
    hvac1000
    Power On = on
    Limit Circuit Open or External Load On "W" =1
    (Does not apply to Deck Switch, see below)
    Pressure Switch Open with Inducer On =2
    Pressure Switch Closed with Inducer On =3
    Ignition Failure (Check Ground)=4
    115 VAC & Neutral Reversed or no Ground =5
    False Flame or Gas Valve Relay Shorted =continuous


    Low Flame Sensor Signal = Continuous Flash
    Flame Present = ON
  • Jun 21, 2008, 10:47 AM
    RUBEN-69
    My Uint Blink 5 Times
  • Jan 3, 2012, 06:11 PM
    nordyne1
    Have westinghouse gas furnace residentiual Nordyne model FG6RA 072C-12A Solid red light when burner ingnights yellow light blinks eight times the burner fuel supply shuts off and blower continues