Question
 
 
#1  
Old Dec 15, 2005, 05:13 PM
Dr D
Senior Member
Dr D is offline
 
Join Date: Dec 2005
Location: Phoenix, AZ
Posts: 687
Dr D See this member's comment history on his/her Profile page.Dr D See this member's comment history on his/her Profile page.
New Install:HW CT3500/new HP w/o heat kit

On my second try, following advice of AC guy and conforming to Honeywell diagram for "4-wire sgl stg HP (jumper intact), I have wired the HP to thermostat as follows: R=R+Rc; O=O; Y=Y+W; G=G; FUEL SWITCH set to E. Nothing works. On my first try I had R=R+Rc; G=G; Y=Y; C (Blue terminal) which should go to Common on tstat I put on B(Changeover in heat). FUEL SWITCH was on F. The fan came on but nothing else.

According to instructions and advice I now have correct connections. The HW book says: do not connect both O & B for sgl stg HP. The C from the HP is a Transformer Common according to HW book.

Could I have fried something on the tstat or the HP? Also I have left the main breaker turned on for the HP. The HP book says that will power Crancase heater to prevent harm at start-up. The AC guy here in sunny Phoenix said not to worry about it. Thanks for any sage advice;this is my first posting.

Reply With Quote
 
     

Answers
 
 
Old Dec 15, 2005, 06:56 PM   #2  
Dogs Expert
labman is offline
 
Join Date: Feb 2003
Location: Northern US
Posts: 10,609
labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.labman See this member's comment history on his/her Profile page.
Y and w usually are cooling and heating. In a conventional system you would never connect them both to the same contact. However, in a heat pump, maybe they just wake up the outside compressor that runs either way. O usually is the mode contact, switching the reversing valves. B or C usually is the other contact from the transformer and a blue wire. G is the fan. It is fairly easy to fry a transformer or blow a fuse. Make sure you have 24 volts between R and B. If not, and you have 120 to the transformer, it is gone. A new one should be less than $20 and easy to find.

Not sure what else to say, go through the directions some more, fool around with the fuel switch. Post back what you find, and maybe I will think of something, or somebody else will have a solution. We don't have a great track record here on heat pumps. Sorry.

You don't want to start up the compressor when it is cold enough to condense the Freon. Having it off long enough to do some troubleshooting shouldn't hurt,

Comments on this post
Dr D agrees: Fixed the problem
  Reply With Quote
 
     
 
 
Old Dec 21, 2005, 03:52 PM   #3  
Senior Member
Dr D is offline
 
Join Date: Dec 2005
Location: Phoenix, AZ
Posts: 687
Dr D See this member's comment history on his/her Profile page.Dr D See this member's comment history on his/her Profile page.
Thank you labman

Sure enough I had no voltage to my thermostat. I got on the roof of my new garage addition and put the VOM to the transformer. 240 volts going in and 0 on the 24 volt output. Today I spent the princely sum of $10.50 on a new transformer, installed it, and lo and behold the AC works and the heat works. I'm a happy camper. Perhaps Honeywell and other manufacturers should put labman on their payroll to write their installation manuals.

Thanks again
  Reply With Quote
 
     


Thread Tools
Display Modes

 
Similar Sponsors

Similar Threads
Question Asker Forum Answers Last Post
Changing from gas heat to electric heat Hadassah24 Heating & Air Conditioning 3 Jun 2, 2007 01:46 PM
Install WIN XP PRO from HDD ismart Windows 7 May 12, 2006 03:27 AM
Can't install AOL notsohandygirl Windows 5 Feb 22, 2006 06:55 AM
install help Snowboarddan123 Electronics 0 Dec 27, 2005 08:42 PM
New Install on Toilet cowboy3084 Plumbing 1 Feb 19, 2005 01:26 PM




Copyright ©2003 - 2007, Ask Me Help Desk.
All times are GMT -8. The time now is 10:57 PM.