    New Honeywell Thermostat, No A/C
    Hi,

    We installed a new Honeywell Thermostat and now we only get hot air blowing from the vents. We are switching from White-Rodgers. Here's the old wires...
    W2 and E = White Wire
    O/B = Orange
    R = Red
    L = Nothing
    G = Green
    C = Blue
    Y = Yellow


    On the new thermostat we have Y, G, Rh, Rc and W. Rh and Rc have a jumper. We tried the following:

    Y = Yellow
    G = Green
    Rh and Rc = Red
    W = White

    We would appreciate any help. It's currently about 90 degrees here.

    Thanks,

    Ashley
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #2

    Aug 30, 2009, 02:23 PM

    Thermostat won't work. You have a heat pump. I don't see a W or W1, so it's probably single stage.
    HVACtechsnj's Avatar
    HVACtechsnj Posts: 11, Reputation: 2
    New Member
     
    #3

    Aug 30, 2009, 02:28 PM

    Its sounds as if you are replacing a heat pump tstat with a gas/oil tstat. The O terminal on the old stat reverses the valve in the outdoor unit from heat to cool or vice versa. Also check to see if a wire was hooked up to w and e. W is the heat using the outdoor unit and e is for emergency heat (electric heat strips) inside air handler. If you have a heat pump you will need to return this stat and buy one that is for heat pump use. Also make sure you turn the power off to the unit before removing or replacing. All newer units have a fuse on the circuit board that is easily blown if two many wires are touched together.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Changed over from White Rodgers Thermostat to Honeywell thermostat [ 3 Answers ]

I have a White Rodgers 2 stage heat/1 cool model 1F58-58 heat pump thermostat that I have changed over to a Honeywell programmable thermostat model RTH7400. Did all the correct wiring as stated in the books but when set to cool, the heater kicks on instead of the central air conditioning. What...

Replacement of Carrier Heat Pump Thermostat with Honeywell TH6000 series thermostat. [ 4 Answers ]

I have a Carrier Series 50QT Electric heat pump that still uses the original non programmable thermostat. I am trying to replace it with Honeywell TH6000 series programmable thermostat. The wiring on the existing Thermostat as follows: O - White, I am thinking this is the Reversing Valve? Y...

Changing over from White Rodgers Thermostat to Honeywell thermostat [ 3 Answers ]

I have a White Rodgers 2 stage heat/1 cool model 1F58-58 heat pump thermostat that I want to change over to a Honeywell programmable thermostat model RTH7400. I need help in trying to figure out the wiring part of this whole thing. Can someone out there please help. I would certainly appreciate...

Rewiring from Weathertron Thermostat to Honeywell Thermostat RTH7500 [ 1 Answers ]

I am trying to replace our current Weathertron THermostat with a Honeywell. We have a heat pump with auxiliary heat and central airconditioning. All the wires matched except the Weathertron had a "T" wire and there is no corresponding connectiion that has a "T" on the Honeywell. I have the "B"...

Honeywell Chronotherm IV Plus Honeywell Thermostat, T8624D [ 1 Answers ]

Honeywell Deluxe Programmable Multistage Thermostat, #T8624D Chronotherm IV Plus I have 2 of above thermostats and have had for about 5 years. It takes no batteries and is directly connected to a 24 volt source. Have one upstairs and one downstairs. Have noticed at times that the LCD on...


View more questions Search