    New furnace leaks when heating, not cooling.
    I'm bought and had installed a new central furnace/ac unit. It is a high efficiency furnace at I think 95%. I have had it for one month. All was fine while I was running the air conditioner. I could see the water running out of the hose into my sump pump. The other night I turned the furnace on as the wife was chilly. It came on and heated just fine. I went down to admire my investment and there was a pool of water around it. I opened the bottom of the unit and seen water dripping from the housing of the blower fan and the bottom of the unit had quite a bit of water standing in it. I called the people out to check it out. He told me the drip tray needed adjustment and the raised the drain tube up about an inch to allow a downhill run for the water. After they left I turned the furnace back on and within half an hour there was water running from above the blower fan and down around it and dripping back to the floor again. I turned the A/C back on to cool the house back down and the drip went away. My thoughts are that if it was the drip tray it would drip more with the a/c on than with the furnace on and that the problem is somewhere in the heating system, not the coils or drip tray.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Sep 25, 2012, 06:31 AM
    I m bought and had installed a new central furnace/ac unit. It is a high effeciency furnace at I think 95%. I have had it for one month. All was fine while I was running the air conditioner. I could see the water running out of the hose into my sump pump. The other night I turned the furnace on as the wife was chilly. It came on and heated just fine. I went down to admire my investment and there was a pool of water around it. I opened the bottom of the unit and seen water dripping from the housing of the blower fan and the bottom of the unit had quite a bit of water standing in it. I called the people out to check it out. He told me the drip tray needed adjustment and the raised the drain tube up about an inch to allow a downhill run for the water. After they left I turned the furnace back on and within half an hour there was water running from above the blower fan and down around it and dripping back to the floor again. I turned the A/C back on to cool the house back down and the drip went away. My thoughts are that if it was the drip tray it would drip more with the a/c on than with the furnace on and that the problem is somewhere in the heating system, not the coils or drip tray.


    The drip is being caused by the furnace itself. It is a condensing furnace and as such creates water vapor as part of the condensing process. You need to have your installer read up on the install manual that came with your furnace and make proper adjustments to the trap or other parts of the furnace itself so it operates properly.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

My Bryant Heating & Cooling furnace circuit baord fuse keep blow out! [ 7 Answers ]

I have Bryant Heating and cooling system. The model is 373LAV. Recently not worked. I checked because the circuit board fuses broken. I replaced one and keep broken. Here is the circuit board model HK42FZ0009. Any one please let me know what maybe the reason for blowing the fuse. Thanks!

Heating and cooling unit blowing air but not heating- goodman [ 1 Answers ]

It is a gas pack. Blowing air but not heating. Could it have a pilot light out?

Blower in furnace works in heating mode, not in cooling mode [ 5 Answers ]

The furnace is an older model Carrier. I do not know at this time the exact model. It is at this time about 20 years old. The central air is a newer Carrier Performance series model. It is two years old. I have checked to make certain the blower moves freely; it does. The blower in the...

Heating and cooling [ 3 Answers ]

My furnace come on and then starts to blow out cold air


View more questions Search