    Limit circuit open
    I have a nordyn furnace. I replace the inducer motor cause it was making a noise and would not run all the time. I also replace a limit switch that is built onto the inducer motor. This limit switch keeps triping and it throws a code of "limit circuit open or external load on "w"." I can disconnect the two wires to the limit switch and short them together and it runs fine. My question is where do I look to fix the problem? I just spent $226.00 for the new inducer motor and limit switch. It's getting expensive.
    wmproop's Avatar
    wmproop Posts: 3,749, Reputation: 91
    Ultra Member
     
    #2

    Oct 23, 2009, 08:16 PM
    The limit switch you are bypassing,, if the furnace works while its bypassed,, must be bad
    Airmergency's Avatar
    Airmergency Posts: 1, Reputation: 1
    New Member
     
    #3

    Jan 11, 2011, 09:06 AM
    I just had the same problem with NORDYNE furnace, one flash L.E.D code on the main board "opening on limit switch" so I took limit out of the furnace and stick my thermometer and read 198F (the limit switch limit is 195F) this proves the limit was GOOD! So I checked the evaporator, filter and the vents all around the house and they where GOOD as well! I also checked the gas pressure to be good. I found out that the furnace will heat lower "189F" with out the air filter! (the air filter is new) IN CONCLUSION FURNACE IS BAD!

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Evcon Furnace Model BGD10016AX Limit Circuit Open [ 5 Answers ]

My furnace gives me this code by flashing the led 4 times which reads on the diagram in it that the limit circuit is open- I cleaned then little buttons that I think are the sensors. The blower won't shut of and just blows cold air- the burners are not igniting when I turn the thermostat way up. ...

Noedyne heater "limit circuit" open [ 20 Answers ]

I have a Nordyne heater which has been working great for the last 4 years. Tonight, however, the blowers are constantly operating even though the thermostat is off. The red indicator light is indicating that the limit circuit is open or there's and external load on "W". Which I think refers to the...

Nordyne Furnace "burner limit circuit open", during A/C operation [ 4 Answers ]

Hi all, Hope this makes sense and required info is present. Any help or suggestions is appreciated, thanks. Furnace brand is Nordyne, about 3 years old, cooling portion model# of unit is JS3BA-036KA. This issue started last week. The A/C still works, but now the blower portion? Doesn't shut...

Furnace "burner limit circuit open", How to fix? [ 2 Answers ]

The furnace in my vacant rental property does not light. The blower runs but the igniter never glows and the gas valve does not open. The LED blinks once which means the burner limit circuit is open. How do I replace the burner limit circuit? Inside the furnace cover I found the electronic...


View more questions Search