    Furnace_Man's Avatar
    Furnace_Man Posts: 2, Reputation: 1
    New Member
     
    #1

    Nov 10, 2011, 06:37 PM
    Jumper wire at furnace to bypass thermostat...
    Hi, I am wondering if anyone has an easy step by step process that I can follow to jumper my thermostat at the furnace. If I do not have access to the thermostat (upstairs and the landlord isn't home, but I am working in the tenants apartment in the basement) and I want to check my manifold pressure, dropout and such how would I do it safely without frying the thermostat? I should put a jumper wire between R and W, but I was told to disconnect the thermostat wire first. Does that mean I disconnect R place my jumper between the 2 and then put R back on? Any help of confirmation of this would be very appreciated!
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #2

    Nov 10, 2011, 06:46 PM
    Simply jump R to W, as you thought. No need to remove the stat wires, just jump r to w and you will create a call for heat. You will now be able to do your manometer testing etc. Just make sure to take the jumper out when your done.
    Furnace_Man's Avatar
    Furnace_Man Posts: 2, Reputation: 1
    New Member
     
    #3

    Nov 10, 2011, 06:54 PM
    Awesome, thank you very much! Ran into that problem today but I just waited long enough for a call for heat and I was able to do all of the checks I had too.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Furnace thermostat needs 24 v wire [ 6 Answers ]

My new White Rogers programmable furnace stat says it needs 24 v dc to run it. I installed it and am using the 2 AA batteries to power it, but I have 4 wires coming in now. I have A/C. The stat is running OK now but if I take the batteries out the display goes dead. I don't know how to run 24 v...

Goodman furnace guso50-2 thermostat wiring instructions for 2 wire thermostat [ 2 Answers ]

Looking to hook up a 2 wire heat only thermostat as the door with the weiring diagram is missing it's a goodman guso50-2?

How do I jumper a TX500B Thermostat, bypass the therm. To see if it's working? [ 6 Answers ]

I hear the thermastat click when I raise the setpoint above the measured temp, but nothing happens. I want to jumper out the therm. just to eliminate it as the problem. From left to right - I have G, Y, W, RH & RC - there is a jumper from RH to RC, with a red wire connected. I do read 28 VAC from...

Honeywell thermostat pro 8000, Why remove jumper wire? [ 2 Answers ]

I'm trying to install a HoneyWell digital thermostat Pro 8000, part number TH8320U108 for my Rudd and Rheem heating and a/c system. The Rudd Furnace is a plain Silhouette and the Rheem a/c is a model 3765SA17. All of the wiring hook up points from the old Honeywell thermostat match the new...


View more questions Search