    Installing double pole wall t-stat baseboard heater
    I have a 220 baseboard heater, and it is on dedicated circuit. Heater works okay as I have run wires straight through and turned on circuit breaker and heater works. This is a Marley baseboard heater and wall double pole thermostat. Instructions with thermostat leave a lot to be desired. Actual wiring from heater to circuit breaker has black and white wire. Thermostat has black and red. Assuming black wires match, and red and white match. For the black and white wires coming from heater, what wire(s) do they connect to on the t-stat, and for the wires going to the circuit breaker, what wires do they connect to on the t-stat? I keep popping the cb.
    Thank you.
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #2

    Nov 26, 2006, 07:07 AM
    Just connect the 2 white wires with a wire nut and switch the black wire with one side of the stat.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #3

    Nov 26, 2006, 07:16 AM
    You need to note on the stat which two wires are LINE and which two wires are LOAD. The two black may be LINE, the two feed wires, black and white will connect to the STAT BLACKS, the two wires going tio the heater will then connect to the STAT REDS.

    A double pole theormostat is a two switches, one for each hot lead, feed the stat on one set of wires, LINE, and continue onto the heater with the LOAD.

    One switch of a double pole stat closes immediately when turned ON, the other switch closes on temperature fall, turning on the heat when the temperature at the stat is calling for heat.

    By connecting the feed to both blacks at the stat is shorting out the circuit.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wiring Hot Tub and using a 50 Amp Double Pole GFCI Circiut Breaker [ 10 Answers ]

:confused: I keep getting the GFCI breaker tripping after wiring my hot tub. I wired 2 hot Red and Black to the proper terminals and the White to the neutral and the Bare Copper to the ground Post at the tub. I am using 6-3 w/G per instructions. Could the GFCI breaker be bad? When I wire...

20 amp double pole gfci [ 9 Answers ]

I am working on an addition and am installing a whirlpool tub. The tub requires 2 - 20 amp GFCI protect circuits: 1 for the pump and 1 for the heater. I ran 12/3 wire in the walls thinking I could have the BLACK wire go from 1 GFCI breaker to the pump outlet and the RED wire go from a 2nd GFCI...

Electrical baseboard heater [ 10 Answers ]

Hi, I am installing two baseboard heaters in an additionn (two separate rooms). I will be running new wire and putting them on the same circuit. The heaters will be 48" 240V rated at 1000 Watts (4.2 amps). My qestions: -What size wire should I use (12/3, 10/3, etc.)? -What should the amp...

Baseboard Heater [ 1 Answers ]

I'm wiring a 240v 1500w heater and I ran a #12 wire because the circuit is also going to double as a A/C circuit for the summer. Anyhow I followed the wiring diagram on heater and wired to a 2pole 15amp and I turned on breaker and it popped so I pulled apart the heater and looked it all over again...

Baseboard heater help [ 2 Answers ]

I have to replace a missing baseboard heater 110 volt 1500 watt all I can find at home depot Lowe's etc is 220 volt can I use one of those hooked to 110 I do understand the output would be lower but actually don't need that much heat in that room anyway Thanks Gene


View more questions Search