    How to connect my 4 wire thermostat to my 5 wire air handler
    I installed a new ceiling mount air handler 7.5 kw goodman 1.5 ton it has 5 thermostat wires coming out... green,red,white,blue,brown... my thermostat wires from my thermostat has 4 wires of red green white yellow... and my condenser unit outside coming in has 2 wires red and green,, and my overflow for condensation shutoff has 2 wires black,and black... could anyone help me figure this out??
    dewey066's Avatar
    dewey066 Posts: 49, Reputation: 1
    Junior Member
     
    #2

    Oct 1, 2013, 05:57 PM
    Is this a mini-split/ductless unit?? Follow the instructions!!

    As far as standard split systems go (inside air handler with ductwork and an outside condenser) this may help:

    Colors don't really matter - it's what both ends are connected to! Here's an attachment from Honeywell (they kind of standardized colors for terminal designations): I would make the R - Red. I would Make the Y yellow, I would make the W white, and you probably have a blue or green - this would be your G. This would require a thermostat that has batteries. If it is AC only then you can take W and connect it to C for power (R and C are power - don't touch them together!! It should be off when you do this). As far as the two black wires - use these to break the Y to the outside condenser: connect a short piece of two-wire thermostat wire to each of the blacks then take the other two ends and use a wire-nut to connect to one side of the "Y" and the other to connect where "Y comes from" (this will also be a two-wire cable going to the outside unit: you need a common "C" and "Y" to turn on the outside unit - these go the two sides of the contactor).
    Attached Images
     

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

2 wire heat thermostat and 2 wire air thermostat want to wire to a programmable [ 1 Answers ]

2 wire heat thermostat and 2 wire air thermostat want to wire both to a programmable thermostat, need wiring information

How to wire Pyne air handler? [ 0 Answers ]

Hi! I have Pyne air handler model PF1M with baseboard waterheater. It has (all: cooling and heating) two zones. Before I had two 3-wire tstats for cooling an two 2-wire tstats for heating. Now I decided to change two (round Honeywell ) tstats downstairs for one combo. Idiots from Honeywell...

How to wire air handler to condenser [ 4 Answers ]

Can you help with how to wire up a air handle and condensing unit


View more questions Search