Ask Experts Questions for FREE Help !
Ask
    banthony155's Avatar
    banthony155 Posts: 2, Reputation: 1
    New Member
     
    #1

    Jan 28, 2008, 07:37 AM
    Hot Water Baseboard Heat, Cold Rooms
    I have hot water base board heat. About a week ago, I noticed I couldn't get the house to go above 62 degrees. When I touch the baseboards the two rooms at the beginning of the loop are hot, but as I go farther through the house the units are colder and colder leaving the two bedrooms freezing cold. Last winter I had a problem with a pipe freezing, so now I keep a small heater on in the basement to avoid this happening again. The circulating pump comes on and is only a year old. As I said the problem started suddenly. What could be wrong? Can I fix it myself?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Jan 28, 2008, 07:54 AM
    Air in the system? Bleed baseboard system.
    Low boiler water pressure? Raise water pressure

    These two items are the cause of the condition you are experiencing.

    There can be others but not likely.
    tsa7man's Avatar
    tsa7man Posts: 154, Reputation: 9
    Junior Member
     
    #3

    Jan 28, 2008, 08:48 AM
    As well, check that the zone valve is open ( if you have one) and the pump is running ? To be noted, just because a pump is running does not mean it is moving water, because of system pressure or air as hvac1000 stated... you may have a frozen pipe section again...
    ghkhlw's Avatar
    ghkhlw Posts: 4, Reputation: 1
    New Member
     
    #4

    Jan 29, 2008, 07:55 PM
    I had the same problem and it was air in the line. There should be bleeders on each heater at one end. If the pump is on all the time just crack that little valve open and see if air comes out. When water starts to come shut off.
    Hawkeye249's Avatar
    Hawkeye249 Posts: 3, Reputation: 1
    New Member
     
    #5

    Oct 23, 2011, 05:27 AM
    Follow-up question: One zone services three bedrooms and a bathroom. First bedroom, bathroom, and second bedroom heat well. Third bedroom at the end of the run is always cold. Its radiator is warm, but not hot. The system does not include valves to regulate water flow by room, only flappers over the pipe/diffusers.
    Can there be air in the third bedroom's pipe when the other rooms are fine?
    Thanks in advance for assisting!

    Beginner at this and presumed the radiators were incorrectly sized causing the water to be cooled too much before reaching the third bedroom. I.E. the system is about twenty years old and it is possible/likely that room was always cold.
    jaylen11's Avatar
    jaylen11 Posts: 1, Reputation: 1
    New Member
     
    #6

    Nov 27, 2012, 08:23 AM
    Three floors in house heat was in all floors than yesterday no heat on first floor heaters are located on third floor all floors have theremaostats
    Hawkeye249's Avatar
    Hawkeye249 Posts: 3, Reputation: 1
    New Member
     
    #7

    Nov 27, 2012, 12:58 PM
    Quote Originally Posted by Hawkeye249 View Post
    Followup question: One zone services three bedrooms and a bathroom. First bedroom, bathroom, and second bedroom heat well. Third bedroom at the end of the run is always cold. Its radiator is warm, but not hot. The system does not include valves to regulate water flow by room, only flappers over the pipe/diffusers.
    Can there be air in the third bedroom's pipe when the other rooms are fine?
    Thanks in advance for assisting!

    Beginner at this and presumed the radiators were incorrectly sized causing the water to be cooled too much before reaching the third bedroom. I.E., the system is about twenty years old and it is possible/likely that room was always cold.
    ANSWERED!

    While adding insulation, I discovered an uninsulated opening between the ceiling of the basement and the floor upstairs. After adding insulation, the cold room is at least 5 degrees warmer, if not more.

    When the house was built, it was properly insulated per the code in effect at the time. It had a wood burning stove in the basement to supplement electric baseboard heat.

    During the winters, the kitchen became quite cold. It was located some distance from the stove on the upper floor. And next to the cold basement.

    To allow more of the stove's heat to reach the kitchen, the insulation was removed from the basement ceiling under the kitchen floor.

    Assume it had some positive effect.

    Later, an oil furnace was added along with associated plumbing to replace the electric baseboards with hot water. And the wood stove was taken out.

    At that time the cold bedroom was discovered. Since it was unoccupied, not a big deal.

    Then we needed to make full time use of it, again.

    I didn't know the history when I added insulation, fixing the problem.
    Was then given the history and all fell into place.
    Hawkeye249's Avatar
    Hawkeye249 Posts: 3, Reputation: 1
    New Member
     
    #8

    Nov 27, 2012, 01:02 PM
    "And next to the cold basement."

    SHOULD HAVE READ

    And next to the cold bedroom.
    bigred04's Avatar
    bigred04 Posts: 1, Reputation: 1
    New Member
     
    #9

    Jan 2, 2013, 05:55 PM
    I have a hot water baseboard system in my house. When I purchase the home it had one zone for the entire house. Since then I have added two additional zones by installing thermostats and zone valves in strategic locations. These modifications worked well for a couple of years. However, recently the zones are not functioning properly. When the thermostat calls for heat the zone valve opens, then once the set temperature has been obtained the zone value remains open. This causes the temperature to continue raising in that zone. I then have to reset the thermostat to a setting higher then the room temperature. This causes the zone valve to actuate to the closed position and back to open in one continuous cycle. I then reset the temperature to the normal setting and the valve closes. After this the valve functions properly. This phenomonom is sporadic and can happen in any one of the zones. I am unable to leave the house for any extended time in fear the heat will come on and not shut off. I recently replaced all thermostats but the problem still exist. What can I do to resolve this problem?
    Grady White's Avatar
    Grady White Posts: 1,417, Reputation: 59
    Ultra Member
     
    #10

    Jan 3, 2013, 07:16 PM
    Bigred04,
    It would be much easier to help you if you would be kind enough to start a new thread with your question. Entitle it something like "Zone Valve problem, hot water baseboard".

    Thanks, Grady White

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Cold water coming out of hot water tap in bathroom but Really hot water in kitchen [ 7 Answers ]

Can anyone give me a reason as to why nearly completely cold water is coming out of my hot water tap in my bathroom but when I run the hot water tap in the kitchen the water is nearly boiling. The hot water and cold water taps are separate in the bathroom, where the kitchen has a handle which...

New hot water heater installed, but no hot water pressure. Plenty of cold water? [ 11 Answers ]

Hi, I own a small plumbing service and have a problem I've never encountered before. I installed a new top vented gas water heater for a customer. Turned the main back on, bled air out of the lines, etc. Problem is there is no hot water pressure throughout the house. Cold water pressure is fine....

Water Rushing through baseboard heat pipes [ 4 Answers ]

We have a Weil Mclain Gold Oil furnace that is approximately four years. The furnace generates heat through our hotwater baseboard heat pipes. Lately we hear the sound of rushing water in the pipes. In the past we have heard banging when the system is cold and heating up, but this is something...

Hot water baseboard [ 1 Answers ]

I want to change a hot water baseboard heater what is the steps imust take thanks

Hot water baseboard [ 1 Answers ]

When the heat is turned on, water is heard rushing through the pipes. The boiler is gas fired.


View more questions Search