  • Oct 24, 2010, 02:06 AM
    Screamin_Eagle
    Honeywell RTH 2300 Thermostat
    Hi, I bought a Honeywell RTH 2300 thermostat and I'm trying to hook it up, the wires I have coming out of the wall are white, green, red, yellow and blue. I hooked up the matching colors to the W, G, R, Y and the blue wire I attached to the O/B. I have the jumpers set as follows: jumper 1 HG and jumper 2 B. There is no hot air coming out when I put the heat on, it just blows out cool air. Am I doing something wrong?
  • Oct 24, 2010, 06:30 AM
    Joshdta

    Blue goes to c, and there must be a jumper from rh to rc.
  • Oct 24, 2010, 12:56 PM
    Screamin_Eagle
    Ok I went and bought the Honeywell RTH2310 which according to the Honeywll tech is compatible for my ac/heat unit. I have a 3 zone forced air unit and now when I turn the heat setting on the boiler does not turn on, and also the a/c unit does not turn on when I set the thermostat to cool. My other 2 zones are working fine.The tech gave me the phone # for the zoned air tech department which is not open on weekends! Any help on why this might be happening? Thanks
  • Oct 24, 2010, 02:47 PM
    Joshdta

    You can't have a forced air boiler. So what do you have a hot water boiler of a forced air gas furnace?? If you have the stat wired correctly then you must have a problem with your many board, or your damper control. Did you change your wiring as I said in the first post?
  • Oct 24, 2010, 03:25 PM
    Screamin_Eagle
    Comment on Joshdta's post
    I have a Burnham V8 series oil heat furnace. I changed the thermostat to the RTH2310 which has the settings for rc&rh. White-W,Green-G,Yellow-Y,Red-RC,Blue-RH. I tried troubleshooting w/ the tech by connecting RH to W RH to Y RC to W RH to Y no luck.
  • Oct 24, 2010, 03:42 PM
    Screamin_Eagle
    How would I check to see if it is the damper control and what is a many board? I have 3 units in the attic and 3 Amana Remote condensing units outside for the ac. I am very new to all of this and would appreciate any help! Thanks
  • Oct 24, 2010, 03:57 PM
    Joshdta

    The blue goes to c. does this furnace have ac on it or is it a separate unit?
  • Oct 24, 2010, 04:50 PM
    Screamin_Eagle
    You keep saying Blue goes to C, this is the manual for the thermostat... customer.honeywell.com/techlit/pdf/PackedLit/69-2214ES.pdf I put Blue to the Rh. The ac unit is separate. I have 3 units in the attic and 3 Amana Remote condensing units outside for the ac.
  • Oct 24, 2010, 06:00 PM
    Joshdta

    OK if you have a wire on rh and one on rc, did you romove the jumper? Just so I am not confused, you have hot water boiler heat? Does the water go to baseboards or hotwater coils in your airhandlers?
  • Oct 24, 2010, 06:20 PM
    Screamin_Eagle
    Yes I removed the jumper and I do have hot water heat. I don't have baseboards so it must go to the coils in the airhandlers (which I have 3 in the attic).
  • Oct 25, 2010, 02:32 PM
    Joshdta

    If you did not turn off the power to the airhandler. Before you changed the stat. then you may have blown a fuse in the attic part.
  • Oct 27, 2010, 06:05 AM
    Screamin_Eagle
    I installed the new thermostat, went up to the attic and switched the wires from the cold relay to the heat relay and now my boiler is kicking on. The problem now is when I shut the thermostat off the fan continues to run. I have what I believe is an aquastat attached to the airhandler with a dial on it that was set to 120, when I turned the dial up to 160 the fan shut off. When I lowered it back to 130 it kicked on again. Even if I pull my thermostat off the wall the fan continues to run. Any one have any answers as to what might be my problem? Please try to be as specific and you can and not give me a one sentence answer that sill keeps me wondering! Thanks
  • Nov 1, 2010, 04:46 PM
    Screamin_Eagle
    No help?
  • Nov 1, 2010, 05:16 PM
    Joshdta

    Not after you being a jack a$$
  • Nov 1, 2010, 05:38 PM
    mygirlsdad77

    With a system such as you describe, it would be near impossible to answer your questions over the phone, let alone the internet. I hate to say it, but this is really a job for an onsite tech. Need to have somebody that can see the set up and get their hands on it. The system you have in your home is not the average (simple) heating system, and will most likely be fixed by way of a service call. Good luck and please let us know how things work out.
  • Nov 2, 2010, 03:22 AM
    Screamin_Eagle
    Comment on Screamin_Eagle's post
    WOW, way to show off how intelligent you are! Why do they let clowns like you post on here?
  • Nov 2, 2010, 04:53 AM
    Joshdta
    Quote:

    Originally Posted by Screamin_Eagle View Post
    No help??


    You don't even know what kind of system you have. You don't stay online long enough for us to ask any questions. Every time you come back on you have a different problem. How are we supposed to know anything about what you are doing. You have never put a make or model of the airhandlers. At this rate you are never going to get anything fixed. And your calling me a idiot. Looks like you're the idiot I have heat.
  • Nov 2, 2010, 06:20 AM
    Screamin_Eagle
    Hey genuis, I don't have to be online for you to post a question! You never asked any questions about the make or model of the airhandlers or I would have posted it. There are people who don't have any experience with heating/ac systems and that is why they come to this website to try to get help from others! Why don't you read your previous replys to me and maybe you'll understand that your not really being that helpful! I think I'll take mygirlsdad77's advice and call a professonal unlike you JOSH!

  • Nov 18, 2010, 01:55 AM
    kace47
    I have a honeywell RTH2310b thermostat and it only has a 5 wire hook up , but I have 6 wires and don't know were the orange and black wires hook up to can you help
  • Nov 18, 2010, 05:26 PM
    mygirlsdad77

    Hi kace47. Please start your own thread, it will have a better chance of getting answers that way. When you do, please give the type of system you have and as much info as possible so we can try our best to help.