Heil 7000 furnace, blower stays on and burners don't ignite

Asked Oct 11, 2009, 01:24 PM — 14 Answers
Furnace Info:
-Upflow Condensing Gas Furnace is a Heil 7000 (model# NUGK075DG09)
-Electric spark or host surface ignitor ( I think it's spark)
-Installed Oct. '96 (when we built the house)
-90% efficiency
-wall thermostat is honeywell programmable. Don't know model but was also purchased in fall of '96


Problem:
I noticed the blower on the furnace hadn't shut off and was still blowing air when it should be off (thermostat fan setting was "auto").
Later, when heat should have been on, I felt cool air blowing out of vents, so then realized it was not blowing heat.
Checked out furnace and burners were not lit.
Then shut off power to furnace so blower would stop.

Called local service. According to my wife who was home, service tech stated he couldn't find the problem and that the furnace started for him.
He then showed my wife a limit switch that could be used to ignite the burners by touching what looks like a small post on the switch. My wife thought he used a screwdirver to touch a post on the switch. I'm not exactly sure which limit switch it is. It is above the burners. I have the manual, but it isn't real clear to me which switch it is (there are 3).
I attached a couple of images with the limit switch circled in red.

By the next morning, furnace wasn't working again, blower was constantly on and no heat.
I used a screwdriver as indicated by the technician on the limit switch to see if the burners would ignite. When touching the switch, it sounded like the exhaust fan started, and a few seconds after that, I could see the spark ignite the burners. But, the burners don't stay lit. As soon as I take the screwdriver away from switch, they turn off. THis was done when the thermostat temp was set high enough that the furnace should be operating.

The description on the invoice left just stated "fix limit on furnace & check operation".
Tech had noted if you had to start the burners more than a couple times by touching the limit switch, we probably need to get a new furnace. That seems a bit extreme and wonder if some component needs to be replaced.

Any suggestions? It's starting to get cool here in and, so need to figure out soon if I should make another service call to see if it can be repaired or start shopping for a new furnace.

Thanks in advance!

Attached Images
  
14 Answers
hvacservicetech_07's Avatar
hvacservicetech_07 Posts: 1,082, Reputation: 414
Ultra Member
 
#11

Oct 12, 2009, 08:02 PM
If the flames are not rolling out,replace the rollout switch.
Helpful  (1)
westsummer's Avatar
westsummer Posts: 1, Reputation: 10
Junior Member
 
#12

Oct 15, 2009, 05:35 PM
We have exactly the same furnace model as yours. Yesterday, we got a similar problem: blower not stopping but burners stopped when temp was about 62F. We had to turn off the power to stop the blower. By reading your post, I tried pressing the small square post (though without trying putting "heat on" last night). Then this afternoon, the furnace started after we set thermostat to "heat on" . But again, burners stopped when temp was about 62F and blower still blowing.

Finally, we reset the thermostat (by pressing the small reset hole button using a key) and found out that its default temp is 62F (it seems that thermostat somehow was not aligned with the furnace). Now burners and the blower work together (twice so far). Hopefully, you have fixed your problem as well.

Thanks for your post.
Helpful
glura's Avatar
glura Posts: 9, Reputation: 1
New Member
 
#13

Oct 23, 2009, 09:06 PM
Our issue was the flame rollout switch.
I emailed the company that was out to check it originally, explained how it was behaving and what I tested, and they sent another person out to re-inspect.
Burners, heat exchanger, and everything else was fine, but the flame rollout switch was bad. He replaced that and tested the furnace operation, and everything checked out fine.

Thanks again hvacservicetech_07!
Helpful
hvacservicetech_07's Avatar
hvacservicetech_07 Posts: 1,082, Reputation: 414
Ultra Member
 
#14

Oct 26, 2009, 05:43 PM
No problem at all. Glad to help!
Helpful
skipsut's Avatar
skipsut Posts: 1, Reputation: 10
Junior Member
 
#15

Dec 2, 2009, 10:19 AM
Where is the flame rollout switch
Helpful

Not your question? Ask your question View similar questions

 
Thread Tools Search this Thread
Search this Thread:

Advanced Search

Add your answer here.

Remove Text Formatting

Undo
Redo
 
Decrease Size
Increase Size
Bold
Italic
Underline
Align Left
Align Center
Align Right
Ordered List
Unordered List
Decrease Indent
Increase Indent
Insert Email Link
Wrap [QUOTE] tags around selected text
Wrap [CODE] tags around selected text
Wrap [HTML] tags around selected text
Wrap [PHP] tags around selected text
Wrap [YOUTUBE] tags around selected text
Notification Type:



Check out some similar questions!

Heil furnace burners go out after a few minutes [ 4 Answers ]

Have A Heil Furnace Model # NULK105AH02 : Serial number: H51118647, 105,000BTU Been having problems getting the burners to stay lit. We've cleaned it completely, put a new electronic switch on it. Still not working properly. It goes off propane, instead of natural gas. We are getting black soot...

Furnace pilot is on, but burners do not ignite [ 1 Answers ]

I have a Carrier furnace 201BB and the pilot comes on but theburners do not ignite all the time. What can I do. Is there a part that needs changed. HELP

Gas burners on furnace do not ignite [ 3 Answers ]

The gas burners on my furnace do not ignite. When I turn on the heat at the thermostat and set the temperature to a setting higher than the room temperature I can hear a faint click within a couple of seconds. Within a few more seconds the blower comes on, but the burners never fire up. There is a...

Gas furnace burners won't ignite [ 4 Answers ]

17 year old gas furnace...burners won't ignite. What are the logical troubleshooting steps to solve this problem?

Main burners on furnace do no ignite [ 6 Answers ]

I have a bryant furnace, model 398. The main burners do not light after the pilot light ignites. I have cleaned the blower motor and everything else I can. Everything looks and sounds good, but the main burners are not getting any gas to them and lighting. Its getting cold in here and need some...


View more Heating & Air Conditioning questions Search