    wisho's Avatar
    wisho Posts: 2, Reputation: 1
    New Member
     
    #1

    Feb 22, 2008, 11:20 AM
    Heater turns on but no flames or heat
    Hello , I have a nordyne ra 80+ upflow/horizontial furnace. Currently my furnace is on but does not give off any heat, rather I see no flames on my furnace. My LED display states there is a fault condition of "Limit circuit open or External load on W" What does that mean. Can anyone shed some light on this matter, I really need some help. Bye for now :(
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Feb 22, 2008, 07:20 PM
    The limit controal is open caused by high temperatuure.
    GE1223's Avatar
    GE1223 Posts: 30, Reputation: 2
    Junior Member
     
    #3

    Feb 23, 2008, 09:33 AM
    Check your air filter, a dirty air filter can cause it to over heat and kick off the high limit. Also check your duct work make sure there are no restrictions for air flow, no kinks or drooping, also make sure there is nothing in front of the return grill inside the house that would block air flow.
    wisho's Avatar
    wisho Posts: 2, Reputation: 1
    New Member
     
    #4

    Feb 23, 2008, 10:57 AM
    Thanks for the suggestion, this happened when I closed all the vents because work was being done on the house. I had some contractors sanding the floor and I did not want the dust getting into the vent. I will make sure to open the vents clean the filter, vacuum the furnace. My other question the furnace does not ignite how do I get it to ignite.
    GE1223's Avatar
    GE1223 Posts: 30, Reputation: 2
    Junior Member
     
    #5

    Feb 23, 2008, 06:46 PM
    After your sure there are no more restrictions to airflow and a clean filter then try cutting power from furnace completely off (t-stat to off) for about 2-5 miniutes then back on this will reset the board. Some limits have a reset button on the limit that you can reset by just pushing the small button. The limit should be located just above the burner assembly. Also try cutting power to furnace completely You may want to send an e-mail to T-Top he is a veteran in the field. I have only been in the field for a couple of years so I am not sure about the reset on the High limit. Some units automatically reset the limit after the furnace cools down. If this does not solve the problem then the limit may have to be replaced.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Heater flames turn on and off [ 7 Answers ]

I have a Day & Night home forced air heater apx 30 years old. Model U-19A. Recently, when the unit is turned on, the pilot light ignites the flames, but they only burn for a few seconds, then shut off. Then they light up again, then shut off. Sometimes they stay on for a period, but most times just...

Hunter 44155C Wiring - A/C turns on during heat cycle or heat will not shut off [ 0 Answers ]

Trying this again with the correct thermostat specs. Sorry, guys! It's a Hunter 44155C and the wires I have going into it are: White - W/B Red - Rh Green - G Yellow - Y1 Jumper from Rh-Rc

Natural gas heater turns off. Thermostat? [ 1 Answers ]

I have a natural gas heater that (I assume) has a thermostat built in. It never seemed to work correctly. Sometimes it would shut off in 30 min and sometimes not at all. NOW, it will only stay lit for about 2 minutes. Any suggestions?

Pilot light turns off when I turn my heater off [ 3 Answers ]

Hi, Hope someone can help with this problem I've been having with my heater. I have a Day & Night heater and whenever I turn the heater off, the pilot light goes off and I have to manually light the pilot each time. Any clues on what could be the problem? Thanks for any help!

Gas Heater Turns and Off every two minutes [ 1 Answers ]

Hello Our Gas Heater turns on and then after a short burst stops. I observed that the Gas flames start and stop every two minutes even though temperature that I set on thermostat has not been reached. Is this normal? Over the long run house heats up to the my require heat but I suspect this...


View more questions Search