    Heat strips
    New heat strips were installed on a Goodman package h.p. and the strips were not working. There was 240v going to the strips and 24v to and from the t-stat. What could be the problem?
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Dec 13, 2006, 10:48 PM
    Open limit on the strips?
    Michael Maher's Avatar
    Michael Maher Posts: 2, Reputation: 1
    New Member
     
    #3

    Dec 14, 2006, 08:03 PM
    No, it is a closed limit. They are brand new and are wired according to the schematic.
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #4

    Dec 14, 2006, 09:05 PM
    If you truly have 240 on the strips, they should heat unless they are open. What have you actually checked with a meter?

    To do simple checks like this you do need some tools. A test light, a meter, or a voltage detector might be the best place to start with. I came across the niftiest gadget for trouble shooting, a voltage detector. They work through the insulation of wires. There are several brands. I have a GB Instruments GVD-505A, less than $15 at Home Depot. Touch it to a hot wire, and the end glows red. Find the doodad that lights it on one side, and not the other, and you have the culprit. You do not have to open up housings and expose electrical contacts. You are looking at where your hand is, not where the meter is. Most people are capable of doing repairs and will get it going and not get hurt if they use a little sense. The voltage detector makes it even easier.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Furring strips vs walls [ 2 Answers ]

I am remodeling my basement and have cement block walls. The walls are in OK shape, the floor is uneven in places. The room is about 10 degrees warmer in winter and cooler in summer than the rest of the house. I am trying to decide if I should use furring strips to attach my drywall to or build...

NO HEAT! Janitrol heat pump and AC system. Changing to Lux Thermostat. Wiring issue. [ 11 Answers ]

I have a Janitrol A/C and heat pump system. I replaced the thermostat with a Lux T9000LC The A/C works fine, but the heater does not. I have it wired as follows: G - Green Y - Yellow W - White RH - Pink B -

Electric Heat-Pump-No heat [ 2 Answers ]

I had a wall-mounted unit installed in a room in may of this summer. In the middle of the night the heat shut off and has not come back on since. It is an Amana, electric heat with heat pump unit. The cooling works, the heating setting does not blow air at all. When I remove the cover it says...

Changing from gas heat to electric heat [ 3 Answers ]

How do you change from Apollo gas heating system to electric heating system?

UL certification advice regarding power strips [ 2 Answers ]

I'm currently in the process of developing a product that incorporates a power strip. The power strip is housed (encased) but physically not altered. If the power strip is UL certified, would my new product need to be recertified anyway or would the UL approval transfer to my product. What are the...


View more questions Search