    Gravity furnace & 2-wire thermostat
    My sister has an ancient Biltwel Gravity Furnace in her basement that just stopped working. For four years she has just jumpered the thermostat wires upstairs to run the furnace. (Thermostat face completely gone.) There are only two wires coming into the thermostat and NO 110 VAC.

    In the basement, I can find NO 110VAC going into the unit. As a gravity unit, there is no blower. When I jumper the two thermostat wires at the gas valve, the unit still doesn't work.

    What am I missing? What opens the gas valve if there is no 110VAC anywhere? What is my next step to get it working? The gas valve also has a pair of wires that goes up into the lit pilot light assembly.

    Thanks!
    acetc's Avatar
    acetc Posts: 1,004, Reputation: 79
    Ultra Member
     
    #2

    Oct 6, 2007, 05:00 PM
    What you have is a pilot generator, this produces a small amount of electrical currant which operates the gas valve through the thermostat, if the pilot is lit and has a good blue flame it is most likely you have a bad generator, (make sure gas valve is turned on )this is the part that is in the flame with the two wires coming from it. To remove this all you have to do is either unscrew a nut at the bottom of it or simply pull it down out of the pilot. Good luck, Mike
    pud's Avatar
    pud Posts: 1, Reputation: 1
    New Member
     
    #3

    Dec 26, 2012, 10:43 PM
    When I jumper the two thermostat wires at the gas valve it goes on when I take it off it goes off

Not your question? Ask your question View similar questions

 

Add your answer here.


Check out some similar questions!

Furnace thermostat needs 24 v wire [ 6 Answers ]

My new White Rogers programmable furnace stat says it needs 24 v dc to run it. I installed it and am using the 2 AA batteries to power it, but I have 4 wires coming in now. I have A/C. The stat is running OK now but if I take the batteries out the display goes dead. I don't know how to run 24 v...

Is this normal? : thermostat & furnace question [ 21 Answers ]

Hi all... Firstly, I read a lot of posts before asking this question... I saw some similar questions but didn't find the answers I needed... It would be very helpful for me if the follwing could be answered (I'm a first time home owner, in the process of learning stuff, pardon my lack of...

Gravity Floor furnace [ 4 Answers ]

I have a pilot light lit and the thermostat is connected, tried switching 2 wires at thermostat but this did nothing. What next please

5-wire thermostat - LOST a few wire labels. HELP! [ 2 Answers ]

I am installing a programmable thermostat (upgrading from a previous programmable that wasn't to our liking. When taking the old thermostat off, I noticed 4 of the 5 wires were labelled. That's a good thing. HOWEVER, when I took the old baseplate off, 2 of the labels fell off (not sure from...

Wiring a 2 wire thermostat to a 4 wire system [ 1 Answers ]

I have a gas furnace equipped with central air.The compressor is shot in the AC unit,and I needed to replace the thermostat so I bought a heating only thermostat.I have the blower and the w wires together on the w terminal designation and the rh on the r terminal designation, and I have the y wire...


View more questions Search