  • Nov 29, 2006, 03:11 PM
    tcassil
    Goodman heating unit problems
    Hello, I have a Goodman :( heating unit in the house that I moved into model GPM100-4.
    When the exhaust fan comes on to clear out the system before the unit will fire up. It makes a clicking sound. I have learned that it's trying to pull a vacuum from the exhaust fan to a safety switch. If I suck on the vacuum hose it will make the switch and the clicking stops unit runs fine. If I don't, it may click fifty times or click until it times out. I have replaced the pressure switch, hose and fan, but still has not changed anything. Just wonder if anybody else has seen this?
    Thanks,
    Tim
  • Nov 29, 2006, 05:38 PM
    NorthernHeat
    There is an obstruction in the vent most likely. Read some of my other posts, pertaining to goodman furnaces.
  • Nov 29, 2006, 06:14 PM
    tcassil
    I have read your other post and have check everything for an obstruction. The hose, the pressure switch, and where the hose attaches to the exhaust fan. I took off the exhaust vent and checked it, it's clear and even tested it with the vent off and it still had the same issuses.
  • Dec 2, 2006, 05:17 PM
    tcassil
    Might this be an issue with the mother-board cutting out a motor relay before the motor gets started?
  • Dec 3, 2006, 05:27 AM
    NorthernHeat
    If everything is clear and the draft inducer is running I would replace the pressure switch
  • Dec 10, 2006, 08:03 PM
    tcassil
    Ok, I changed the pressure switch and it still clicks about 50 times to start the fan:confused: . I can still suck on the rubber hose and the fan starts right up. What should be my next step?

    Thanks,
    Tim
  • Dec 10, 2006, 09:34 PM
    turnerwest
    Quote:

    Originally Posted by tcassil
    Hello, I have a Goodman :( heating unit in the house that I moved into model GPM100-4.
    When the exhaust fan comes on to clear out the system before the unit will fire up. It makes a clicking sound. I have learned that it's trying to pull a vacuum from the exhaust fan to a safety switch. If I suck on the vacuum hose it will make the switch and the clicking stops unit runs fine. If I don't, it may click fifty times or click until it times out. I have replaced the pressure switch, hose and fan, but still has not changed anything. Just wonder if anybody else has seen this?
    Thanks,
    Tim

    Tim, you say it's a house you moved into... How old is the furnace and has anyone changed or touched the furnace flue? Eric
  • Dec 10, 2006, 10:36 PM
    tcassil
    The furnace is about 4 years, this is my second winter in this house. As far as the flue, I have taken it off and ran it with out it to see if this changed anything (only for a short amount off time and then put it back on) but even with the flue off it's doing the same thing. If it's doing it without the flue, would that show that the flue is not blocked.
    Last winter it made the clicking sound three or six times to start up. I just thought that was bad. Now it can do it for 2 or 3 minutes, before I get off my butt and go suck on the pressure switch hose. It's kind of a running joke with my faimly, but it's starting to suck(haha). I'm afraid that it's going t leave us without any heat some day soon.
    Thanks,
    Tim
  • Dec 11, 2006, 04:53 AM
    labman
    Have you identified just which component is clicking? Sometime you can tell if a relay is chattering by holding your hand on it. Note, sometimes relays have hot contacts on or around them.

    Have you tried a new rubber hose?
  • Dec 11, 2006, 04:20 PM
    NorthernHeat
    Is it 90% efficient and is it on LP?
  • Dec 25, 2006, 09:35 PM
    accurate air
    Quote:

    Originally Posted by tcassil
    Hello, I have a Goodman :( heating unit in the house that I moved into model GPM100-4.
    When the exhaust fan comes on to clear out the system before the unit will fire up. It makes a clicking sound. I have learned that it’s trying to pull a vacuum from the exhaust fan to a safety switch. If I suck on the vacuum hose it will make the switch and the clicking stops unit runs fine. If I don't, it may click fifty times or click until it times out. I have replaced the pressure switch, hose and fan, but still has not changed anything. Just wonder if anybody else has seen this?
    Thanks,
    Tim

    On the inducer housing where the vacuum hose connects the small barbed fitting I have seen that there is a ball inside at back of that fitting the inner side which is acting as a check vavle that sometimes gets corroded and seizes causing the pressure switch not to open I have in the past drilled this fitting out veryy carefullly and removed this ball check vavle you will probably have to remove the inducer assembly to check & do this. Hope this solvesyour problem [email protected]
  • Dec 26, 2006, 05:35 AM
    NorthernHeat
    Quote:

    Originally Posted by accurate air
    On the inducer housing where the vaccum hose connects the small barbed fitting I have seen that there is a ball inside at back of that fitting the inner side which is acting as a check vavle that sometimes gets corroded and seizes causing the pressure switch not to open i have in the past drilled this fitting out veryy carefullly and removed this ball check vavle you will probably have to remove the inducer assembly to check & do this. hope this solvesyour problem [email protected]

    Sorry. There is no check valve in any inducer draft blower that I have ever seen. You are right about it rusting closed though. Just make sure the flue vacuum hose and ports are open and clear. If you can't find the problem the vacuum switch may be bad.